Bosch Rexroth AG
Technical data
NOTICE
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide (SO
and hydrogen suphide (H
NOTICE
To avoid overheating and a trouble-free operation of the product, the ambient air
has to circulate. Also refer to
This is a product that corresponds to the limit values of the emitted
interference of class A (industrial environments), but not of class B
(residential area and small enterprises).
When using the product in residential areas or small enterprises, the
operator has to take actions to prevent radio interferences (also re-
fer to DIN EN 55022).
7 Technical data
Weight
Degree of protection
Tab. 7-1: Technical data
7.1 Voltage supply and current consumption
The following specifications include the values acc. to EN 61131-2.
Infeed U
L
Maximum voltage range allowed
Current consumption from U
Power consumption from U
Reverse voltage protection of the supply voltage
Fuse protection
Transient protection
Voltage dips at current supply interfaces
Electrical isolation and isolation of the voltage ranges
Profibus extension module
24 V supply with FE to XF8
8/37
Defective product due to gases jeopardizing
functions
S)). The product is not resistant against these gases.
2
Failure of the product due to overheating
chapter 10.2 "Installation notes" on page 16
0.120 kg
IP 20 acc. to DIN EN 60 529
L
L
Extension Modules Profibus, RT-
Ethernet, Sercos, CAN
24 V DC PELV/SELV (safety extra-low voltage)
18 V DC to 31.2 V DC (incl. all tolerances and rip-
ple)
0.2 A max.
4.8 W max.
Diode
Internal protective fuse, 4 A
Present, suppressor diodes
Up to 10 ms without impairment
845 V AC, 50 Hz, 1 min
DOK-CONTRL -XFE**EXTMOD-IT04-EN-P
)
2