16.4
MENU SET H CONTROL MODES
16.4.1
CONTROL SOURCE
This setting is not used on the EcoShield Water heater and should not be altered.
16.4.2
CASCADE ADDRESS
This setting is not used on the EcoShield Water heater and should not be altered.
16.4.3
MAX CASCADE SETPOINT
This setting is not used on the EcoShield Water heater and should not be altered.
16.4.4
CASCADE OFFSET
This setting is not used on the EcoShield Water heater and should not be altered.
16.4.5
CASCADE OFF-ON DIFFERENTIAL
This setting is not used on the EcoShield Water heater and should not be altered.
16.5
MENU SET I
16.5.1
DHW PUMP DELAY
The DHW pump delay parameter sets the length of time the DHW (Primary) pump will run after a heater demand
has been satisfied. The time range for this parameter is 0 minutes to 40 minutes and is adjustable (in 10 second
steps) using the Up or Down buttons. Once the desired time setting has been selected, the Enter/Reset button
should be pressed to store the value. The default pump delay is 30 seconds.
16.6
MENU SET J SERVICE NOTIFICATION
16.6.1
SERVICE NOTIFICATION IN MONTHS
When the water heater control determines that a scheduled service is due based on days of installation, the water
heater display will alternate the standard water heater display text with the message SERVICE DUE every 5
seconds. This parameter is adjustable in 1-month intervals using the Up or Down buttons and then stored by
pressing the Enter/Reset button. The time range for this parameter is 0 months to 36 months. The default
service interval is 12 months.
16.6.2
SERVICE NOTIFICATION RUNNING HOURS
When the water heater control determines that a scheduled service is due based on the hours of actual operation,
the water heater display will alternate the standard water heater display text with the message SERVICE DUE
every 5 seconds. This parameter is adjustable in 500-hour intervals using the Up or Down buttons and then
stored by pressing the Enter/Reset button. The time range for this parameter is 0 hours to 100,000 hours. The
default time is 10,000 hours.
16.6.3
SERVICE NOTIFICATION BOILER CYCLES
When the water heater control determines that a scheduled service is due based on the number of water heater
cycles, the water heater display will alternate the standard water heater display text with the message SERVICE
DUE every 5 seconds. This parameter is adjustable in 500 cycle intervals using the Up or Down buttons and then
stored by pressing the Enter/Reset button. The range for this parameter is 0 cycles to 100,000 cycles. The
default is 10,000 cycles.
CIRCULATION PUMPS
42