100273038_2000529317 Rev_B Installation & Operation Manual Models: SIT040DW - SIT119DW This manual must only be used by WARNING a qualified heating installer / service technician. Read all instructions LOW LEAD CONTENT before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation & Operation Manual Please read before proceeding Installer – Read all instructions before • Installation and service must be performed by a qualified WARNING installing. Perform steps in the order given. installer, service agency, or the gas supplier. Have this indirect water heater serviced/ Failure to adhere to the guidelines on this WARNING inspected by a qualified service technician, at...
Installation & Operation Manual General information Double-wall heat exchanger The Lochinvar SIT DW series indirect water heater (FIG. 1-1) is designed to generate domestic hot water in conjunction with a hot water boiler using forced boiler water circulation. Uniform plumbing code...
Characteristic Min. Max. installed in a drain pan suitable for water heaters. Lochinvar shall not be held liable for any such water damage. The tank may be located some distance from the boiler Chloride (PPM) provided the pump is designed to provide the flow called for in Table 3B - Pressure Drop Values, through the coil.
Installation & Operation Manual Boiler side piping DHW prioritization Figures 3-1 thru 3-4 show typical boiler side piping for several common situations. Regardless of which system is This piping system is designed to provide direct hot water used it is imperative that the flow rates called for in Table priority over the other zones in the heating system.
Installation & Operation Manual Boiler side piping (continued) Figure 3-1 Piping Diagram Zoned with Circulators ZONE #1 PRESSURE PRESSURE REDUCING VALVE GAUGE ZONE #2 ZONE #3 ZONE #4 BACKFLOW PREVENTER ZONE CIRCULATORS (TYPICAL) MAKE UP WATER SYSTEM SUPPLY SENSOR (WHEN USED) AIR SEPARATOR EXPANSION TANK...
Page 8
Installation & Operation Manual Boiler side piping Figure 3-2 Piping Diagram Zoned with Valves ZONE #1 PRESSURE PRESSURE REDUCING VALVE GAUGE ZONE #2 ZONE #4 ZONE #3 BACKFLOW PREVENTER ZONE VALVES (TYPICAL) SYSTEM SUPPLY SENSOR MAKE UP WATER (WHEN USED) DIFFERENTIAL PRESSURE BYPASS AIR SEPARATOR...
Page 9
Installation & Operation Manual Boiler side piping (continued) Figure 3-3 Knight Boiler Primary / Secondary Piping PRESSURE REDUCING VALVE BACKFLOW PRESSURE PREVENTER GAUGE MAKE UP WATER SEPARATOR SYSTEM SUPPLY SENSOR FROM SYSTEM SYSTEM SYSTEM BALL VALVE CIRCULATOR Y-STRAINER (TYPICAL) (RECOMMENDED) EXPANSION TANK BOILER...
Page 10
Installation & Operation Manual Boiler side piping Figure 3-4 Multiple Tank Connections PRESSURE REDUCING VALVE BACKFLOW PREVENTER PRESSURE GAUGE MAKEUP WATER SEPARATOR SYSTEM SUPPLY SENSOR FROM SYSTEM SYSTEM NOT TO EXCEED 4 PIPE DIA. SYSTEM OR A MAXIMUM OF 12” APART CIRCULATOR BALL VALVE Y-STRAINER...
Installation & Operation Manual Domestic side (tank) piping Basic domestic piping Domestic water piping for distant fixtures Figure 4-2 on page 13 shows typical domestic water piping In some cases the furthest fixture may be quite distant from for a tank. The function of the components shown are as the tank.
SIT040/050DW - 3/4" NPT with a minimum CSA Rating of 105,000 Btu/hr. SIT065/080/119DW - 3/4" NPT with a minimum CSA Rating of 200,000 Btu/hr. The Lochinvar SIT DW series water heaters NOTICE will absorb/store less than 200,000 Btu/hr when DRAIN domestic water outlet temperature is 210°F...
Page 13
Installation & Operation Manual Domestic side (tank) piping (continued) T&P relief valve discharge piping MUST NOT be: Table 4A - excessively long. Using more than two (2) elbows or 15 Minimum Relief Valve (CSA Rating) feet of piping can reduce discharge capacity. - directly connected to a drain.
Installation & Operation Manual Wiring Indirect water heater sensor setup (Knight boiler) Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and CAUTION dangerous operation. The sensor supplied contains an Auto Reset High Limit (194°F). NOTICE Connect tank sensor Install tank sensor...
Indirect water heater controlled using Aquastat and zone circulator / valve 1. Install Aquastat to tank. Aquastat control (100208546) can be ordered from your local Lochinvar distributor. 2. Connect Aquastat to the zone controller for the Indirect Water Heater Zone.
Installation & Operation Manual Start-up and check-out 1. Make sure the system is free of leaks and that air is purged from the system. Fix any leaks found before proceeding CAUTION further. Leakage from the boiler piping can result in severe damage to the boiler. 2.
Installation & Operation Manual Maintenance The Lochinvar SIT DW series indirect water heater is an Homeowner monthly maintenance to include: extremely simple device and as such requires very little Visually check valves, pipes, and fittings for leaks. Call a maintenance.
Installation & Operation Manual Performance data Table 8A AHRI Chart Squire Indirect DW Water Heater AHRI Rating Minimum Heat Potable Heat Source Minimum Tank Heat Indirect Standby Continuous Output Rate Water Water First Hour Heat Source Source Water Heater Heat Loss Draw Rating from Volume...
Installation & Operation Manual Performance data (continued) How to properly Size Your Indirect Water Heater Use the First Hour Rating (FHR) to properly size your Indirect Water Heater. The First Hour Rating is the amount of hot water in gallons the heater can supply per hour (starting with a tank full of hot water), depending on tank capacity, source of heat, and the size of the burner.
Revision Notes: Revision A (Process #3000001798_Change #500002025) initial release. Revision B (PCP# 3000006451 / CN# 500006731) reflects the addition of the CSA 1-91 logo to the front cover. MM #100273038_DIR #2000529317 Rev B 02/17 - Printed in U.S.A.