7.6 EQUIPMENT GAS SYSTEM LEAK CHECK

An approved gas-inlet appliance isolating valve and union should be installed for each unit in a
convenient and safe position and be clearly marked. Ensure that the gas-inlet appliance isolating valve is in
the OFF position. Although the equipment receives a gas leak check and gas train component integrity check
prior to leaving the factory, transit and installation may cause disturbance to unions, fittings and components.
During commissioning a further test for tightness should be carried out on the equipment gas pipework and
components.
Care must be taken not to allow leak detection fluid on or near any electrical parts or connections.
8.0

FLUE SYSTEM

Location
Description
A
Directly below an opening, air brick, opening windows etc.
B
Above an opening, air brick, opening windows etc.
C
Horizontally to an opening, air brick, opening windows etc.
D
Below a gutter or sanitary pipework
E
Below the eaves
F
Below a balcony or car port roof
G
From a vertical drain or soil pipe
H
From an internal or external corner
I
Above ground, roof or balcony level
J
From a surface facing the terminal
K
From a terminal facing the terminal
From an opening in the car port (e.g. door, window) into the
L
dwelling
M
Vertically from a terminal on the same wall
N
Horizontally from a terminal on the same wall
P
From a vertical structure on the roof
Q
Above intersection with the roof
FIGURE 8.1:
FLUE TERMINAL POSITIONS
TABLE 8.1
FLUE TERMINAL MINIMUM DISTANCES
SHW45-325CE
SHW60-325CE
300
300
300
75
200
200
150
300
300
600
1200
1200
1500
300
300
300
SHW85-435CE
SHW115-435CE
SHW145-435CE
2000
1000
1000
75
200
200
150
300
300
1000
2000
1200
1500
600
300
300
13