Siemens Solkor 7PG2113 Technical Manual page 233

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

Calculated Timing values in seconds for TM =1.0
Curve
IEC-NI
IEC-VI
IEC-EI
IEC-LTI
ANSI-MI
ANSI-VI
ANSI-EI
Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a
Follower DTL applied.
2.7.3.1
Element Blocking
The Derived Earth Fault elements can be blocked by Binary Input Inhibit, VT Supervision and Inrush Detector
operation. The Characteristic can be made non-directional by VT Supervision. This functionality should be
checked.
Element
51N-1
51N-2
51N-3
51N-4
50N-1
50N-2
50N-3
50N-4
©2012 Siemens Protection Devices Limited
2 xIs
10.03
13.50
26.67
120.00
3.80
7.03
9.52
Table 2.7-4
Standard Timings
BI Inhibits
Table 2.7-5
51N Element Blocking
7PG2113/4/5/6 Commissioning & Maintenance
VTS action
5 xIs
4.28
3.38
3.33
30.00
1.69
1.31
1.30
Inrush Detector
Chapter 6 Page 35 of 77