Binary Input Points
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Default Static Variation reported when variation 0 requested: 2 (Binary Input with flags)
Default Change Event Variation reported when variation 0 requested: 2 (Binary Input with absolute time)
Point
Index
62
51G-2
63
50G-2
64
CTS Alarm
65
46IT
66
46DT
67
47-1
68
47-2
69
46BC
70
27/59-1
71
27/59-2
72
27/59-3
73
27/59-4
74
59NIT
75
59NDT
80
Auto-reclose active
81
CB on by auto reclose
82
Reclaim
83
Lockout
86
51-3
87
50-3
88
51N-3
89
50N-3
90
51G-3
91
50G-3
92
51-4
93
50-4
94
51N-4
95
50N-4
96
51G-4
97
50G-4
98
Cold Load Active
99
E/F Protection Out
100
P/F Inst Protection Inhibited
101
E/F Inst Protection Inhibited
©2010 Siemens Protection Devices Limited
Name/Description
7PG2113/4/5/6 Data Communications
Default
Change Event
Assigned Class
(1, 2, 3 or none)
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2