Binary Output Status Points
Static Object Number: 10
Change Event Object Number: 11
Default Variation reported when variation 0 requested: 2 (Binary Output with flags)
Default Change Event variation 0 requested: 2 (Binary Output absolute time)
Control Relay Output Blocks
Object Number: 12
Point
Index
43
Hot line working on/off
44
E/F off/on
45
SEF off/on
46
Inst Protection off/on
48
Reset CB Total Trip Count
49
Reset CB Delta Trip Count
50
Reset CB Count to AR Block
51
Reset Frequent Ops Count
53
Reset I^2t CB Wear
54
CB 1
55
CB 1 Trip & Reclose
56
CB 1 Trip & Lockout
5.5
Analogue Inputs
The following table lists Analog Inputs (Object 30). It is important to note that 16-bit and 32-bit variations of
Analog Inputs, Analog Output Control Blocks, and Analog Output Statuses are transmitted through DNP as
signed numbers.
The "Default Deadband," and the "Default Change Event Assigned Class" columns are used to represent the
absolute amount by which the point must change before an analog change event will be generated, and once
generated in which class poll (1, 2, 3, or none) will the change event be reported.
The default analog input event buffer size is set 30.
©2010 Siemens Protection Devices Limited
Name/Description
7PG2113/4/5/6 Data Communications
Default
Chang
e Event
Supported Control Relay
Assign
Output Block Fields
ed
Class
1
Pulse
On/Pulse
On/Latch Off
1
Pulse
On/Pulse
On/Latch Off
1
Pulse
On/Pulse
On/Latch Off
1
Pulse
On/Pulse
On/Latch Off
1
Pulse On/Latch Off
1
Pulse On/Latch Off
1
Pulse On/Latch Off
1
Pulse On/Latch Off
1
Pulse On/Latch Off
1
Pulse
On/Pulse
On/Latch Off
1
Pulse On/Latch Off
1
Pulse On/Latch Off
Chapter 4 Page 34 of 38
Off/Latch
Off/Latch
Off/Latch
Off/Latch
Off/Latch