8.
The control panel can now be disconnected from the drive.
Download Application Parameters
To download application parameters only to the control panel
from the VFD, perform the following procedure:
1.
Install the control panel with the correct parameters onto
the VFD.
2.
Select MENU (SOFT KEY 2). The main menu will be
displayed.
3.
Use the UP or DOWN keys to highlight PAR BACKUP on
the display screen and press ENTER (SOFT KEY 2).
4.
Use the UP or DOWN keys to highlight DOWNLOAD
APPLICATION and press SEL (SOFT KEY 2).
5.
The text "Downloading Parameters (partial)" will be dis-
played with a progress indicator. To stop the process,
select ABORT (SOFT KEY 1).
6.
When the download is complete, the text "Parameter
download successful" will be displayed.
7.
The display will then return to the PAR BACKUP menu.
Select EXIT (SOFT KEY 1) to return to the main menu.
8.
The control panel can now be disconnected from the drive.
CLOCK SET MODE
The clock set mode is used for setting the date and time for the
internal clock of the VFD. In order to use the timer functions of
the VFD control, the internal clock must be set. The date is
used to determine weekdays and is visible in the fault logs.
To set the clock, perform the following procedure:
1.
Select MENU (SOFT KEY 2). The main menu will be
displayed.
2.
Use the UP or DOWN keys to highlight CLOCK SET on
the display screen and press ENTER (SOFT KEY 2). The
clock set parameter list will be displayed.
3.
Use the UP or DOWN keys to highlight CLOCK VISI-
BILITY and press SEL (SOFT KEY 2). This parameter is
used to display or hide the clock on the screen. Use the UP
or DOWN keys to change the parameter setting. Press OK
(SOFT KEY 2) to save the configuration and return to the
Clock Set menu.
4.
Use the UP or DOWN keys to highlight SET TIME and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
PARAMETER
PARAMETER
GROUP
NUMBER
9902
9905
9906
START-UP
DATA
9907
9908
9909
1001
START/STOP/
DIR
1003
1103
REFERENCE
1104
SELECT
1105
Table A — 48LC 04 VFD Parameters
UNIT SIZE
Motor Description
1.7 HP 575v
Drive/Motor Voltage
575v
Motor Part Number
HD56FR579
VFD Part Number
HK30WA048
ACH550-
ABB Part Number
CARUH
-03A9-6
(1) HVAC
Application Macro
DEFAULT
Motor Nominal
575
Voltage
Motor Nominal
3.1
Current
Motor Nominal
60
Frequency
Motor Nominal
1725
Speed
Motor Nominal Power
1.7
EXT1 Commands
(1) DI1
Direction
(1) Forward
REF1 Select
(1) AI1
REF1 Minimum
0 Hz
REF1 Maximum
60 Hz
change the hours and minutes. Press OK (SOFT KEY 2) to
save the configuration and return to the Clock Set menu.
5.
Use the UP or DOWN keys to highlight TIME FORMAT
and press SEL (SOFT KEY 2). Use the UP or DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
6.
Use the UP or DOWN keys to highlight SET DATE and
press SEL (SOFT KEY 2). Use the UP or DOWN keys to
change the day, month, and year. Press OK (SOFT KEY 2)
to save the configuration and return to the Clock Set menu.
7.
Use the UP or DOWN keys to highlight DATE FORMAT
and press SEL (SOFT KEY 2). Use the UP or DOWN
keys to change the parameter setting. Press OK (SOFT
KEY 2) to save the configuration and return to the Clock
Set menu.
8.
Press EXIT (SOFT KEY 1) twice to return to the main
menu.
I/O SETTINGS MODE
The I/O Settings mode is used for viewing and editing the I/O
settings.
To configure the I/O settings, perform the following procedure:
1.
Select MENU (SOFT KEY 2). The main menu will be
displayed.
2.
Use the UP or DOWN keys to highlight I/O SETTINGS
on the display screen and press ENTER (SOFT KEY 2).
The I/O Settings parameter list will be displayed.
3.
Use the UP or DOWN keys to highlight the desired I/O
setting and press SEL (SOFT KEY 2).
4.
Use the UP or DOWN keys to select the parameter to
view. Press OK (SOFT KEY 2).
5.
Use the UP or DOWN keys to change the parameter set-
ting. Press SAVE (SOFT KEY 2) to save the configura-
tion. Press CANCEL (SOFT KEY 1) to keep the previous
value. Any modifications that are not saved will not be
changed.
6.
Press EXIT (SOFT KEY 1) twice to return to the main
menu.
48LC 04
1.7 HP 208-230v
1.7 HP 460v
208-230v
460v
HD56FR233
HD56FR463
HK30WA045
HK30WA046
ACH550-
ACH550-
CARUH
CARUH
-07A5-2
-04A-4
(1) HVAC
(1) HVAC
DEFAULT
DEFAULT
230
460
5.8
2.9
60
60
1725
1725
1.7
1.7
(1) DI1
(1) DI1
(1) Forward
(1) Forward
(1) AI1
(1) AI1
0 Hz
0 Hz
60 Hz
60 Hz
38
2.4 HP 575v
2.4 HP 208-230v
575v
208-230v
HD56FE577
HD56FE653
HK30WA048
HK30WA001
ACH550-
ACH550-
CARUH
CARUH
-03A9-6
-012A-2
(1) HVAC
(1) HVAC
DEFAULT
DEFAULT
575
230
3.4
7.9
60
60
1725
1725
2.4
2.4
(1) DI1
(1) DI1
(1) Forward
(1) Forward
(1) AI1
(1) AI1
0 Hz
0 Hz
60 Hz
60 Hz