Step 7 - Convert To Horizontal And Connect Ductwork (When Required) - Carrier WeatherExpert 48LC 04 Series Installation Instructions Manual

Single package rooftop gas heating/electric cooling unit with puron (r-410a) refrigerant
Table of Contents

Advertisement

CAUTION - NOTICE TO RIGGERS:
AVERTISSEMENT - REMARQUE À
L'ATTENTION DES MONTEURS
TOUS LES CAPOTS DOIVENT ÊTRE EN PLACE AVANT LE LEVAGE
• Hook rigging shackles through holes in base rail, as shown in Detail "A".
• Use wooden top skid, when rigging, to prevent rigging straps from damaging unit.
• Max weight includes base unit plus shipping pallet plus all available FIOP's which could
be on that size unit.
• "B" dimension is based on base unit (PAC no heat or YAC w/low heat) plus economizer
option only. This dimension may vary slightly with units configured with other FIOP
options.
• Spreader bars required to lift and transport the unit.
• Accrocher les manilles des élingues de levages dans les trous situés dans le rail
de base comme indiqué au Détail « A ».
• Utiliser des cales en bois lors du levage pour éviter que les élingues n'endommagent
le haut de l'appareil.
• Le poids maximum inclut la configuration de base, le poids de la palette d'expédition,
ainsi que toutes les options pouvant être installées en usine (FIOP) pour la
plateforme sélectionnée.
• La dimension de "B" provient de la configuration de base (PAC sans chauffage ou
YAC chauffage au gaz natufrel) qui inclut l'option economizer seulement. Cette
dimension peut varier légèrement en fonction des différentes options sélectionnées,
installées en usine (FIOP).
• Barres d'écartement requises pour soulever et transporter l'unité.
"B"
REQUIRED
SPREADER
BARS
MODEL
50LC_004
50LC_005
50LC_006
48LC_004
48LC_005
48LC_006
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without
factory-installed economizer or return-air smoke detector op-
tion may be field-converted to horizontal ducted configuration.
To convert to horizontal configuration, remove screws from
side duct opening covers (see Fig. 10) and remove covers. Use
the screws to install the covers on vertical duct openings with
the insulation-side down. The panels must be inserted into the
notches on the basepan to properly seal. The notches are cov-
ered by the tape used to secure the insulation to the basepan
and are not easily seen. See Fig. 11 for position of the notches
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
914-1371
(36"- 54")
"C"
"A"
SEE DETAIL "A"
VOIR DÉTAIL « A »
MAX WEIGHT
LB
700
830
865
760
895
930
Fig. 9 — Rigging Label
PLACE ALL SEAL STRIP IN PLACE
BEFORE PLACING UNIT ON ROOF CURB.
INSTALLER TOUTES LES BANDES
D'ISOLATION EN PLACE AVANT DE
PLACER L'APPAREIL SUR LE REBORD
DE TOIT.
DUCT END
PASSAGES CONDUITES
A
KG
IN
MM
IN
318
74.5
1890
36.5
377
74.5
1890
36.5
393
74.5
1890
36.0
345
74.5
1890
38.0
407
74.5
1890
38.0
423
74.5
1890
37.5
in the basepan. Seals around duct openings must be tight. Se-
cure with screws as shown in Fig. 12. Cover seams with foil
duct tape.
Field-supplied flanges should be attached to horizontal duct
openings and all ductwork should be secured to the flanges. In-
sulate and weatherproof all external ductwork, joints, and roof
or building openings with counter flashing and mastic in accor-
dance with applicable codes.
Do not cover or obscure visibility to the unit's informative data
plate when insulating horizontal ductwork.
12
DETAIL A
DÉTAIL « A »
B
C
MM
IN
MM
925
33.5
850
925
41.5
1055
915
41.5
1055
965
33.5
850
965
41.5
1055
955
41.5
1055
48HC500030 A