Start Up by Changing Parameters Individually
Initial start-up is performed at the factory. To start up the VFD
by changing individual parameters, perform the following pro-
cedure:
1.
Select MENU (SOFT KEY 2). The Main menu will be
displayed.
2.
Use the UP or DOWN keys to highlight PARAMETERS
on the display screen and press ENTER (SOFT KEY 2).
3.
Use the UP or DOWN keys to highlight the desired
parameter group and press SEL (SOFT KEY 2).
4.
Use the UP or DOWN keys to highlight the desired
parameter and press EDIT (SOFT KEY 2).
5.
Use the UP or DOWN keys to change the value of the
parameter.
6.
Press SAVE (SOFT KEY 2) to store the modified value.
Press CANCEL (SOFT KEY 1) to keep the previous
value. Any modifications that are not saved will not be
changed.
7.
Choose another parameter or press EXIT (SOFT KEY 1)
to return to the listing of parameter groups. Continue until
all the parameters have been configured and then press
EXIT (SOFT KEY 1) to return to the main menu.
NOTE: The current parameter value appears above the highlight
parameter. To view the default parameter value, press the UP and
DOWN keys simultaneously. To restore the default factory set-
tings, select the application macro "HVAC Default."
RJ-45 (CAT5) Cable
(Bundled with Control Harness)
Fig. B — Location of VFD in 48LC 04-06 Units
36
VFD Modes
The VFD has several different modes for configuring, operat-
ing, and diagnosing the VFD. The modes are:
Standard Display mode—shows drive status information
and operates the drive
Parameters mode—edits parameter values individually
Start-up Assistant mode—guides the start up and configu-
ration. DO NOT USE THE START-UP ASSISTANT ON
THESE LC UNITS!
Changed Parameters mode—shows all changed parameters
Drive Parameter Backup mode—stores or uploads the
parameters
Clock Set mode—sets the time and date for the drive
I/O Settings mode—checks and edits the I/O settings
STANDARD DISPLAY MODE
Use the standard display mode to read information on the drive
status and operate the drive. To reach the standard display
mode, press EXIT until the LCD display shows status informa-
tion as described below. (See Fig. C.)
The top line of the LCD display shows the basic status infor-
mation of the drive. The HAND icon indicates that the drive
control is local from the control panel. The AUTO icon indi-
cates that the drive is in remote control mode, such as the basic
I/O or field bus.
ABB VFD
w/ Remote Keypad