Outdoor Unit Fault - Fujitsu Waterstage WS G140DC6 Series Maintenance Document

Air to water heat pump. split system (single phase type). split system (3-phase type).
Table of Contents

Advertisement

Split system (Single phase and 3-phase type)

2.1.2 Outdoor Unit Fault

When the system is switched back on after a power
outage, the Hydraulic Unit may display fault 370 for a
few tens of seconds. This is not a serious problem. It
simply means that the outdoor unit is running its
tests. Once the tests have been completed, the fault
should disappear.
On the outdoor unit
When an error occurs:
-
The diode "ERROR" (2) blinks
Press once on the switch "ENTER" (SW4)
-
The "ERROR" (2) diode blinks several times depending on the error's type
LED display
Hydraulic Unit
Green
Red
1 flash
1 flash
4 flashes
1 flash
4 flashes
2 flashes
6 flashes
3 flashes
6 flashes
4 flashes
7 flashes
1 flash
7 flashes
2 flashes
7 flashes
3 flashes
7 flashes
4 flashes
7 flashes
7 flashes
7 flashes
8 flashes
8 flashes
6 flashes
9 flashes
4 flashes
9 flashes
5 flashes
9 flashes
7 flashes
10 flashes
1 flash
10 flashes 3 flashes
10 flashes 5 flashes
Continuous flashing
Continuous
Off
lighting
8
LED display on the outdoor unit (single phase and 3-phase)
Diagnosis
Outdoor unit
Off
Serial reverse transfer error.
1 flash
Serial forward transfer error.
22 flashes
Heat pump capacity signal error
22 flashes
Hydraulic Unit Heat ex. Sensor error
18 flashes
Inverter error.
Active filter error (single phase)
19 flashes
P.F.C. error (3-phase)
2 flashes
Discharge thermistor error.
8 flashes
Compressor thermistor error.
5 flashes
Heat-exchange thermistor (intermediate) error.
4 flashes
Heat-exchange thermistor (outlet) error.
7 flashes
Outdoor temperature thermistor error.
9 flashes
Heat sink thermistor error.
6 flashes
Expansion valve thermistor error.
3 flashes
Pressure sensor error.
13 flashes
Current trip (permanent stoppage).
14 flashes
Detection of compressor position error (permanent stoppage).
15 flashes
Compressor start up error (permanent stoppage).
16 flashes
Outdoor unit fan 1 motor error.
17 flashes
Outdoor unit fan 2 motor error.
11 flashes
Discharge temperature protection (permanent stoppage).
12 flashes
Compressor temperature protection (permanent stoppage).
20 flashes
Low pressure abnormal.
Pump down operation.
Defrosting.
If it doesn't, if a fault has occurred on the outdoor unit
as indicated by the Hydraulic Unit, you must remove
the front (right-hand) facing from the outdoor unit.
Faults are coded by LED flashes. Error messages are
listed in the table below:
Maintenance Document 1544-1
Clear
1
2
4
5
20
21
27
7
11
12
8
9
10
14
24
15
33
17
18
22
25
26