Installation Of The Outdoor Unit; Installation Precautions - Fujitsu Waterstage WOYA060LFCA Installation And Operating Manual

Air to water heat pump, split system
Hide thumbs Also See for Waterstage WOYA060LFCA:
Table of Contents

Advertisement

Air to Water Heat Pump, split system
2 .4

Installation of the outdoor unit

2 .4 .1 Installation precautions

" The outdoor unit must only be installed outdoor
(outdoors). If a shelter is required, it must have
broad openings on the 4 walls and observe the
installation clearances
• Choose the location of the appliance after discussion
with the client.
• Choose a site that is preferably sunny and sheltered
from
strong
cold
predominant
tramontana, etc...).
• The unit must be easily accessible for future installation
and maintenance work
• Ensure that it is possible to make the connections to
the hydraulic unit easily.
• The outdoor unit is able to withstand bad weather but
avoid installing in a position where it is likely to be
exposed to significant dirt or flowing water (under a
defective gutter for example).
" Models Comfort 5, 6 & 8
" Model Comfort 10
600 mm
Minimum
or more
figure 13 - Minimum installation clearances around outdoor unit (models extensa + 5, 6, 8 & 10)
Installation and operation manual "1764 - EN"
(figure
13).
winds
(mistral,
(figure
13).
100 mm
Minimum
or more
• Water may drain away from the outdoor unit when it
is operating. Do not install the appliance on a paved
terrace; choose a well-drained place (e.g. gravel
or sand). If the installation is in an area where the
temperature can be lower than 0°C for a long period,
check that the presence of ice does not present any
danger. A drainage pipe can also be connected to the
outdoor unit
(see figure 14, page
• Nothing should obstruct the air circulation through the
evaporator and from the fan
• Keep the outdoor unit away from heat sources and
inflammable products.
• Make sure the appliance not disturb the surrounding
area or users (noise level, draught generated, low
temperature of the air being blown out, with the risk of
freezing plants in its path).
100 mm
Minimum
or more
300 mm
or more
Minimum
250 mm
300 mm
Minimum
or more
Minimum
or more
250 mm
Minimum
or more
17).
(figure
13).
300 mm
Minimum
or more
- 15 -