Fan Motor Removal; Valve Cover Removal - Fujitsu Waterstage WS G140DC6 Series Maintenance Document

Air to water heat pump. split system (single phase type). split system (3-phase type).
Table of Contents

Advertisement

Split system (Single phase and 3-phase type)

6.1.5 FAN MOTOR removal

Remove the 4 mounting screws.
Cut the binder. (2 places)

6.1.6 VALVE COVER removal

Hook (4 places)
Remove the mounting screws
96
Remove the FAN GUARD by
sliding upward.
Loose the clamp. (2 places) and
remove the lead wires.
screw
Remove the VALVE COVER.
Remove the Hex Socket Screw. And
remove the PROPELLER FAN.
Note at the installation.
Insert propeller Fan and Moter shalf
reference D cutting position.
And the tightening torque at the
installation.
Tightening torque is from 10 to 15 N.M.
Remove the 4 mounting screws.