Table 12 Electrical Specifications W**Ac - Bard W42AC-A Installation Instructions Manual

Wall mount air conditioner
Hide thumbs Also See for W42AC-A:
Table of Contents

Advertisement

Rated
No. Field
Volts
MODEL
Power
&
Circuits
Phase
W42AC-A00, A0Z
1
A05
1
A10
230/208-1
1
A15
1 or 2
A20
1 or 2
W42AC-B00, B0Z
1
B06
1
B09
1
230/208-3
B15
1
B18
1 or 2
W42AC-C00, C0Z
1
C09
460-3
1
C15
1
W48AC-A00, A0Z
1
A05
1
A10
1
230/208-1
A15
1 or 2
A20
1 or 2
W48AC-B00, B0Z
1
B06
1
B09
1
230/208-3
B15
1
B18
1 or 2
W48AC-C00, C0Z
1
C09
1
460-3
C15
1
W60AC-A00, A0Z
1
A05
1
A10
230/208-1
1
A15
1 or 2
A20
1 or 2
W60AC-B00, B0Z
1
B06
1
B09
230/208-3
1
B15
1
B18
1 or 2
W60AC-C00, C0Z
1
C09
1
460-3
C15
1
W72AC-A00, A0Z
1
A05
1
A10
1
230/208-1
A15
1 or 2
A20
1 or 2
W72AC-B00, B0Z
1
B06
1
B09
1
230/208-3
B15
1
B18
1 or 2
W72AC-C00, C0Z
1
C09
460-3
1
C15
1
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention
to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a
raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Manual 2100-692
Page
32 of 40
Electrical Specifications − W**AC Series
Single Circuit
Maximum
Field
Minimum
External
Power
Ground
Circuit
Fuse or
Wire
Wire
Ampacity
Ckt. Brkr.
Size
31
50
8
10
31
50
8
10
57
60
6
10
83
90
4
109
120
2
23
35
8
10
23
35
8
10
32
35
8
10
51
60
6
10
60
60
6
10
12
15
14
14
17
20
12
12
26
30
10
10
35
50
8
10
35
50
8
10
59
60
6
10
85
90
4
111
120
2
25
35
8
10
25
35
8
10
34
40
8
10
52
60
6
10
61
70
6
12
15
14
14
17
20
12
12
26
30
10
10
38
50
8
10
38
50
8
10
59
60
6
10
85
90
4
111
125
2
28
40
8
10
28
40
8
10
34
40
8
10
52
60
6
10
61
70
6
14
20
12
12
18
30
10
10
26
30
10
10
56
60
6
10
56
60
6
10
60
70
6
86
90
3
112
120
2
38
40
8
10
38
40
8
10
38
40
8
10
53
60
6
10
62
70
6
18
20
12
12
18
20
12
12
27
30
10
10
TABLE 12
 Minimum
 Maximum
Circuit
External Fuse or
Ampacity
Ckt. Breaker
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
8
57
26
60
6
57
52
60
8
60
30
60
6
60
52
60
8
8
38
52
40
6
59
52
60
8
34
28
40
8
56
26
60
8
56
52
60
6
60
52
26
60
8
38
28
40
Multiple Circuit
Field Power
Wire Size
30
6
10
60
6
6
30
6
10
60
6
6
60
8
6
60
6
6
30
8
10
30
6
10
30
6
0
60
6
6
30
8
10
Ground
Wire Size
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10