Installation and Operation Guide SOLECTRIA XGI 1000 (Rev D)
AC High Frequency
7
1 Detected
AC Very High
8
Frequency 2
Detected
AC Low Voltage 1
9
Detected
AC Very Low
10
Voltage 2 Detected
AC Extremely Low
11
Voltage 3 Detected
AC High Voltage 1
12
Detected
DOCR-070733-D
AC high frequency region 1
detected.
AC high frequency region 2
detected.
AC low voltage region 1 detected.
AC low voltage region 2 detected.
AC low voltage region 3 detected.
AC high voltage region 1 detected.
Using a CAT III multi-meter verify
the AC frequency. If there is a
discrepancy of greater than 2%
between the measured results and
the frequency reported by the
inverter contact Technical Support,
otherwise wait for the grid
conditions to improve.
Using a CAT III multi-meter verify
the AC frequency. If there is a
discrepancy of greater than 2%
between the measured results and
the frequency reported by the
inverter contact Technical Support,
otherwise wait for the grid
conditions to improve.
Using a CAT III multi-meter verify
the AC voltage. If there is a
discrepancy of greater than 2%
between the measured results and
the voltage reported by the inverter
contact Technical Support,
otherwise wait for the grid
conditions to improve.
Using a CAT III multi-meter verify
the AC voltage. If there is a
discrepancy of greater than 2%
between the measured results and
the voltage reported by the inverter
contact Technical Support,
otherwise wait for the grid
conditions to improve.
Using a CAT III multi-meter verify
the AC voltage. If there is a
discrepancy of greater than 2%
between the measured results and
the voltage reported by the inverter
contact Technical Support,
otherwise wait for the grid
conditions to improve.
Using a CAT III multi-meter verify
the AC voltage. If there is a
discrepancy of greater than 2%
between the measured results and
the voltage reported by the inverter
contact Technical Support,
otherwise wait for the grid
conditions to improve.