Trane Tracer TD7 User Manual page 23

With uc 800 for rthd chillers
Hide thumbs Also See for Tracer TD7:
Table of Contents

Advertisement

Hex
Diagnostic Name
Code
Low Evaporator Water
C5
Temp (Unit Off)
Low Evaporator
6B3
Temp: Unit Off
Low Evaporator Water
C6
Temp (Unit On)
Evaporator Water
384
Flow Overdue
Evaporator Water
ED
Flow Lost
Condenser Water
DC
Flow Overdue
Condenser Water
F7
Flow Lost
High Evaporator
6B8
Refrigerant Pressure
RLC-SVU006A-E4
Effects
Severity
Persistence
Target
Info and
Chiller
Special
NonLatch
Action
Info and
Chiller
Special
NonLatch
Action
Immediate
Chiller
and Special
NonLatch
Action
Chiller
Normal
NonLatch
Chiller
Immediate
NonLatch
Chiller
Normal
NonLatch
Chiller
Immediate
NonLatch
Immediate
Chiller
and Special
NonLatch
Action
Active Modes
[Inactive Modes]
The leaving Evaporator water temp. fell
below the leaving water temp cutout setting
Unit in Stop Mode,
for 30 degree F seconds while the Chiller is
or in Auto Mode
in the Stop mode, or in Auto mode with no
and No Ckt(s)
compressors running. Energize Evap Water
Energized
pump Relay until diagnostic auto resets,
[Any Ckt
then return to normal evap pump control.
Energized]
Automatic reset occurs when the temp rises
2°F (1.1°C) above the cutout setting for
30 minutes.
The evap sat temp fell below the water temp
cutout setting while the respective evap
liquid level was greater than –21.2 mm for
30 (or 150 begining with rev 08) degree F
Unit in Stop Mode,
seconds while Chiller is in the Stop mode, or
or in Auto Mode
in Auto mode with no compressors running.
and No Ckt's
Energize Evap Water pump Relay until
Energizd
diagnostic auto resets, then return to normal
[Any Ckt Energizd]
evap pump control. Automatic reset occurs
when either the evap temp rises 2°F (1.1°C)
above the cutout setting or the liquid level
falls below –21.2mm for 30 minutes
The Evaporator water temp. fell below the
cutout setpoint for 30 degree F Seconds
Any Ckt[s]
while the compressor was running. Automatic
Energized
reset occurs when the temperature rises
[No Ckt(s)
2°F (1.1°C) above the cutout setting for
Energizd]
2 minutes. This diagnostic shall not de-
energize the Evaporator Water Pump Output.
Evaporator water fl ow was not proven within
20 minutes of the Evaporator water pump
Estab. Evap. Water
relay being energized. The Evap pump
Flow on going from
command status will not be effected. This
STOP to AUTO.
diagnostic will auto-clear on proof of fl ow
(6-10 seconds of continuous fl ow), or if
chiller is returned to Stop mode.
The Evaporator water fl ow proof input was
open for more than 6-10 contiguous seconds
after fl ow had been proven. The pump
Evap pump
command status will not be effected. Even
commanded "on"
though the pump may be commanded to run
except for
in the STOP modes (pump off delay time),
[All Stop modes]
this diagnostic shall not be called out in the
STOP modes. This diagnostic will auto-clear
on proof of fl ow (6-10 seconds of continuous
fl ow), or if chiller is returned to Stop mode.
Condenser water fl ow was not proven within
20 minutes of the condenser pump relay
Estab Cond Water
being energized. The Cond Pump shall be
Flow
commanded off. Diagnostic is reset with
return of fl ow (although only possible with
external control of pump)
The condenser water fl ow proof input was
open for more than 6 contiguous seconds
after fl ow had been proven. This diagnostic
Start and All Run
is automatically cleared once the compressor
Modes
is stopped by a fi xed time out of 7 sec. The
Cond Pump shall be commanded off but the
Evap pump command will not be effected.
The evaporator refrigerant pressure has
risen above 190 psig (future use – add "for
continuous15 seconds"). The evaporator
water pump relay will be de-energized to
stop the pump regardless of why the pump
All
is running. The diagnostic will auto reset
and the pump will return to normal control
when the evaporator pressures falls below
185 psig. This diagnostic must shutdown the
chiller if it is running.
Diagnostics
Reset
Criteria
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Local
23