Trane Tracer TD7 User Manual page 22

With uc 800 for rthd chillers
Hide thumbs Also See for Tracer TD7:
Table of Contents

Advertisement

Diagnostics
Hex
Diagnostic Name
Code
External Chilled/Hot
87
Water Setpoint
External Current Limit
89
Setpoint
AFD output power
702
input
External Base Loading
4C4
Setpoint
Evap Water Flow
8A
(Entering Water
Temp)
Evaporator Entering
8E
Water Temp Sensor
Evaporator Leaving
AB
Water Temp Sensor
Condenser Entering
9A
Water Temp Sensor
Condenser Leaving
9B
Water Temp Sensor
Condenser Rfgt
5B8
Pressure Transducer
Evaporator Rfgt
5BA
Pressure Transducer
Oil Pressure
5BE
Transducer
Oil Flow Protection
1E1
Fault
Low Evaporator
B5
Refrigerant Pressure
22
Effects
Severity
Persistence
Target
Chiller
Info
NonLatch
Chiller
Info
NonLatch
Chiller
Info
NonLatch
Info and
Chiller
Special
NonLatch
Action
Chiller
Info
NonLatch
Info and
Chiller
Special
Latch
Action
Chiller
Normal
Latch
Info and
Chiller
Special
Latch
Action
Chiller
Info
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Immediate
Latch
Chiller
Immediate
Latch
Active Modes
[Inactive Modes]
a. Function Not "Enabled": no diagnostics. b.
"Enabled": Out-Of-Range Low or Hi or bad
LLID, set diagnostic, default CWS to next
All
level of priority (e.g. Front Panel SetPoint).
This Info diagnostic will automatically reset if
the input returns to the normal range.
a. Not "Enabled": no diagnostics. b.
"Enabled": Out-Of-Range Low or Hi or bad
LLID, set diagnostic, default CLS to next level
All
of priority (e.g. Front Panel SetPoint. This
Info diagnostic will automatically reset if the
input returns to the normal range.
Out-Of-Range Low or Hi or bad LLID,
set diagnostic, This Info diagnostic will
All
automatically reset if the input returns to the
normal range.
a. Not "Enabled": no diagnostics. b.
"Enabled": Out-Of-Range Low or Hi or bad
LLID, set diagnostic, default BLS to next level
All
of priority (e.g. Front Panel SetPoint. This
Info diagnostic will automatically reset if the
input returns to the normal range.
The entering evaporator water temp fell
below the leaving evaporator water temp.
Any Ckt(s)
by more than 2°F for 100°F-sec. For falling
Energized
fi lm evaporators this diagnostic cannot
[No Ckt(s)
reliably indicate loss of fl ow, but can warn
Energized]
of improper fl ow direction through the
evaporator, misbound temperature sensors,
or other system problems
Bad Sensor or LLID Normal operation unless
CHW Reset is enabled. If CHW Reset is
enabled and either Return or Constant Return
Chilled Water Reset is selected, its effect will
be removed but slew rates on the change will
be limited per the Chilled Water Reset spec.
All
Bad Sensor or LLID
Bad Sensor or LLID. If chiller running, and
All
condenser water regulating valve option
installed, force valve to 100% fl ow.
All
Bad Sensor or LLID
All
Bad Sensor or LLID
All
Bad Sensor or LLID
All
Bad Sensor or LLID
The Oil Pressure Transducer for this Chiller
Starter Contactor
is reading a pressure either above its
Energized [all Stop
Condenser Pressure by 15 Psia or more, or
modes]
below its Evaporator Pressure 10 Psia or
more for 30 seconds continuously.
The Evaporator Refrigerant Pressure dropped
below 10 psia just prior to compressor
Chiller Prestart and
start. The pressure fell below 10 psia while
Chiller Energized
running but before the 3 minute ignore time
had expired or fell below 16 Psia after the
3 minute ignore time had expired.
Reset
Criteria
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Local
Local
RLC-SVU006A-E4

Hide quick links:

Advertisement

Table of Contents