Trane Tracer TD7 User Manual page 27

With uc 800 for rthd chillers
Hide thumbs Also See for Tracer TD7:
Table of Contents

Advertisement

Hex
Diagnostic Name
Code
Comm Loss: High
5EB
Pressure Cutout
Switch
Comm Loss:
5EF
Evaporator Water
Flow Switch
Comm Loss:
6B6
Condenser Water
Flow Switch
Comm Loss:
5F0
Evaporator Rfgt
Pressure
Comm Loss:
5F2
Condenser Rfgt
Pressure
Comm Loss: Oil
5F4
Pressure
Comm Loss: Oil
6B6
Return Gas Pump Fill
Comm Loss: Oil
6B6
Return Gas Pump
Drain
Comm Loss: Oil Loss
6B6
Level sensor Input
Comm Loss: Master
6B6
Oil Line SV
Comm Loss:
5F8
Evaporator Water
Pump Relay
Comm Loss:
6B6
Condenser Water
Pump Relay
Comm Loss: SSS/AFD
6B6
Fault
Comm Loss:
6B6
Refrigerant Monitor
Input
Comm Loss: Ext Base
6B6
Loading Setpoint
Comm Loss: Ext Base
6B6
Loading Command
Comm Loss:
688
Evaporator Rfgt
Liquid Level
690
Comm Loss: Starter
RLC-SVU006A-E4
Effects
Severity
Persistence
Chiller
Normal
Latch
Chiller
Immediate
Latch
Chiller
Immediate
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Normal
Latch
Chiller
Info
Latch
Chiller
Info
Latch
Chiller
Info
Latch
Chiller
Info
Latch
Info and
Chiller
Special
Latch
Action
Info and
Chiller
Special
Latch
Action
Chiller
Normal
Latch
Chiller
Immediate
Latch
Active Modes
[Inactive Modes]
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between
the MP and the Functional ID has occurred
for a 30 second period. The external
All
base load setpoint input is removed from
the arbitration to establish the Base
LoadingSetpoint.
Continual loss of communication between
the MP and the Functional ID has occurred
All
for a 30 second period. The external base
load input is removed from the arbitration to
enable Base Loading.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Continual loss of communication between the
All
MP and the Functional ID has occurred for a
30 second period.
Diagnostics
Reset
Criteria
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Local