Table 6.
Local Heat Only With No Fan Present
Configuration
Local
Remote
PWM electric
Not applicable
(1 to 3 stages)
SCR electric
Not applicable
On/Off electric
Not applicable
(1 to 3 stages)
On/Off hot
water
Not applicable
(1 stage)
Modulating hot
Not applicable
water
Table 7.
Local Heat Only With Parallel Fan Present
Configuration
Local
Remote Fan
Not
Fan
applicable
Fan and PWM
Not
electric (1 to 3
applicable
stages)
Not
SCR electric
applicable
VAV-SVX07B-EN
Stage 1
• Local PI capacity loop
• Each stage represents an equal percentage of total capacity PWM Output (one stage = 100%; two
stages = 50% each; three stages = 33.33% each)
• Total capacity is limited by communicated supply heat control
• Local PI capacity loop
• SCR heat capacity = total
capacity
• Total capacity limited by
communicated supply heat
control
Local thermostatic:
• On: Zt < HSP
• Off: Zt HSP + 0.5 °F (0.28°C)
Each stage represents an equal percentage of total capacity. Total capacity is limited by communicated
supply heat control.
Local thermostatic:
• On: Zt < HSP
• Off: Zt HSP + 0.5°F (0.28°C)
Total capacity is limited by
communicated supply heat control
• Local PI capacity loop
Modulating valve capacity = Total capacity
Valve drive incrementally open/closed
Total capacity limited by communicated supply heat control
Method of Control
Stage 1
Parallel fan
Not applicable
• Local PI capacity loop.
• Each stage represents an equal
percentage of total capacity PWM
Output (one stage = 100%; two
Parallel fan
stages = 50% each; three stages
= 33.33% each).
• Total capacity is limited by
communicated supply heat
control.
• Local PI
capacity
loop
• SCR heat
capacity =
total
capacity
Not applicable
• Total
capacity
limited by
communica
ted supply
heat control
Calibration, Operation Modes, and Control
Method of Control
Stage2
Not applicable
Local thermostatic:
• On: Zt <HSP - 1°F (0.56°C)
• Off: Zt HSP - 0.5°F (0.28°C)
Not applicable
Not applicable
Stage 2
Not applicable
• Local PI capacity loop.
• Each stage represents an equal percent of total capacity
• (1 stage = 100%, 2 stages = 50% each).
• PWM output.
Total capacity is limited by communicated supply heat control.
Not applicable
Stage 3
Not applicable
Local thermostatic:
• On: Zt < HSP - 2°F
• Off: Zt HSP - 1.5°F (16.9°C)
Not applicable
Not applicable
Not applicable
Stage 3
Not applicable
SCR electric
51