Wiring Best Practices - Trane Tracer Uc

Programmable bacnet controller for variable-air-volume (vav) units
Table of Contents

Advertisement

Figure 1. BACnet MS/TP Link Wiring
+
Tracer SC
+
+
Trane BACnet terminator

Wiring Best Practices

To ensure proper network communication, follow the recommended wiring and best practices
below when installing communication wire:
Note: For more details, refer to the Unit Controller Wiring for the Tracer SC™ System Controller
VAV-SVX07B-EN
BI
LINK
AI
AI
AI
AI
AI
UC400
Sensor
All wiring must comply with the National Electrical Code™ (NEC) and local codes.
Ensure that 24 Vac power supplies are consistent in regards to grounding. Avoid sharing 24 Vac
between controllers.
Avoid over tightening cable ties and other forms of cable wraps. This can damage the wires
inside the cable.
Do not run communication cable alongside or in the same conduit as 24 Vac power. This
includes the conductors running from TRIAC-type inputs.
In open plenums, avoid running wire near lighting ballasts, especially those using 277 Vac.
Use same communication wire type, without terminators, for the zone sensor communication
stubs from the UC400 controller IMC terminals to the zone sensor communication module.
Zone Sensor communication wiring length limits of 300 ft. (100 m).
Wiring Guide (BAS-SVN03).
IM
+
VDC
IMC
BI
LINK
IMC
AI
AI
AI
AI
AI
P
P
LINK
IM
TX
RX
SERVI
SERVICE TOOL
UC400
Zone
Zone
Sensor
+
+
VDC
VDC
BI
BI
LINK
LINK
IMC
IMC
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
P
P
P
P
TX
TX
RX
RX
SERVICE TOOL
SERVICE TOOL
Wiring Installation
IM
+
+
VDC
VDC
BI
LINK
IMC
AI
AI
AI
AI
AI
P
P
P
P
LINK
IM
TX
RX
SERVI
SERVICE TOOL
UC400
Zone
Sensor
Zone sensor
communications
IM
IM
jack wiring
LINK
LINK
IM
IM
SERVI
SERVI
IM
+
LINK
IM
TX
RX
SERVI
SERVICE TOOL
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tracer uc400

Table of Contents