Controller Status Tab - Trane Tracer Uc

Programmable bacnet controller for variable-air-volume (vav) units
Table of Contents

Advertisement

Controller Status Tab

Program
The Tracer UC400 controller has up to three (3) TGP2 programs downloaded and defined in the
factory as part of the factory commissioning process. The three programs are a base program for
damper control, fan, and reheat control. When looking at programming section of Controller Status
tab, operation of these programs can be monitored.
Grid Columns
Applications
Shows status of TGP2 resources.
Expansion Module Status
Shows status of any connected expansion modules. Expansion modules are not required for
factory VAV operation, but can be added to control additional points.
Controller
Lists identifying and status information for the controller including Product Name, Product Version,
Hardware Part Number, Hardware Serial Number, Application Part Number, Application Version,
Application Build Number, Boot Part Number, Boot Version, Boot Build, Unit Sales Order Number,
Model Number, and System Build. The System Build number is the version indicator for factory
points and programs.
VAV-SVX07B-EN
Model: Displays the model number of the controller.
Profile: VAV control sequence profile.
BAS Communication: Displays the status of communications with the Tracer SC.
Instance: Displays the sequence instance assigned to the program. Instance numbers are
assigned based on the order that programs are downloaded to the controller.
Name: Displays the name of the program.
State: Indicates whether the program is Paused or Ready (to execute).
Status: Displays the current operating status, such as idle or running.
Run Type: Indicates whether the program runs at a specified interval (Scheduled) or only when
triggered by an event (Triggered).
Interval: Displays the run frequency of the program starts (for example, 10 seconds).
Note: Ensure the value is greater than the Latency value. If the interval is not long enough, it
can be adjusted on the Program Properties dialog box in the TGP2 Editor.
Duration: Displays the time it takes for the program to run from the first instruction to the last
instruction.
Error: Displays the operational state, whether Execution Halted Normally, Paused, or Error
Terminated.
Control: Clicking Pause button allows user to pause program. When paused, the button
becomes Resume. Clicking Resume will re-start program execution.
TGP2 Status: Displays the operational state of the TGP2 program engine in which all
programs execute.
TGP2 Resources: Displays the amount of memory consumed by the programs.
Tracer™ UC400 Controller Operations
33