Load Connections; Load Cable Selection - Shindaiwa DG1000MI Owner's And Operator's Manual

Vertical, water-cooled 4-cycle diesel engine
Hide thumbs Also See for DG1000MI:
Table of Contents

Advertisement

7.

Load Connections

7-1. Load Cable Selection

CAUTION : PROPERTY DAMAGE
Cable burnout can occur due to generated heat if the load current exceeds
the allowable current of the cable.
The voltage drop between cables is large if the cable is excessively long or
thin, resulting in decreased input voltage to equipment using the generator,
thereby causing decreased performance, faulty operation and malfunction.
Select cable for use that has sufficient thickness and an allowable current possible for use,
giving consideration to the distance from the generator to the equipment using the generator.
< NOTE >
Select cable with a thickness that ensures that the voltage drop across the cable will be within 5%
of the rated voltage.
Expedient Formula: the voltage drop of cables
3-Phase 3-Wire
Voltage Drop (V) =
1-Phase 2-Wire
Voltage Drop (V) =
1
Length (m)
×
58
Dia (mm
1
Length (m)
×
58
Dia (mm
19
× Current (A) × √3
2
)
× Current (A) ×2
2
)