5. Communication Programming
5.1. How to set master module
SoftMaster-NM Link Parameter setting
When using Pnet master module, it is easy to set device region and data size to
communicate between CPU module and communication module (Master module and
Slave module) by using SoftMaster-NM.
The following table describes Pnet High-speed Link setting contents.
Contents
Communication
module setting
Communication
period setting
(Period Type)
Output data
setting when
emergency
Communication
module setting
Mode
Station Number
Communication
type
Read area
(Master module
 Slave
module)
50
Pnet I/F Module 2MLL-PSRA, 2MLL-PSEA User's Guide
Table 14 – Pnet High-speed Link setting contents
Module
Type
Base No.
Slot No.
Select among 20ms, 50ms, 100ms, 200ms, 500ms, 1s, 5s, 10s -default is
20ms.
CPU
Error
CPU
Stop
Sending: transfers data from Master module to Slave module.
Receiving: transfers data from Slave module to Master module.
Slave Station Number (Range: 1 ~ 99)
Indicate communication type between Master and Slave. (Poll, Bit-Strobe,
COS, Cyclic)
Address
Size
(Byte)
Honeywell
High-speed Link
Select Pnet
Maximum: 0 ~ 7, Setting range differ according to CPU
module.
Maximum: 0 ~ 11, Setting rage differ according to base Type.
Latch
Maintain previous output status.
Clear
Clear all output.
Latch
Maintain previous output status.
Clear
Clear all output.
first device of TX devices
Refer to ML200R User's Guide for memory address.
Indicate I/O point into Byte.
- Consider less than 8 bit I/O module as 1 Byte
R210
November 2011