Summary of Contents for Honeywell 2MLF-HO2A
Page 1
Honeywell Process Solutions 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide 2MLF-HO2A, 2MLF-HD2A R200 May 2010 Release 200 Honeywell...
Page 2
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Page 3
May 2010 HO2A, 2MLF- HD2A References The following list identifies all documents that may be sources of reference for material discussed in this publication. Document Title SoftMaster User’s Guide R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 4
Honeywell Global TAC – India Phone: +91-20- 6603-9400 Fascimile: +91-20- 6603-9800 Mail: Honeywell Automation India Ltd 56 and 57, Hadapsar Industrial Estate Hadapsar, Pune –411 013, India Email: Global-TAC-India@honeywell.com 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 6
20th Floor, 1-16-1 Kaigan, Minato-ku, Tokyo 105-0022, Japan Email: Global-TAC-JapanJA25@honeywell.com Elsewhere Call your nearest Honeywell office. World Wide Web Honeywell Solution Support Online: http://www.honeywell.com/ps Training Classes Honeywell Automation College: http://www.automationcollege.com 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 7
WARNING symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 8
Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. viii 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Example of DC12V NPN Open Collector Output Wiring ............60 Example of DC24V PNP Open Collector output wiring ............61 Example of Line Driver Output Wiring .................. 62 OPERATING PROCEDURES AND MONITORING ..... 63 R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
PROGRAMMING ................. 99 Overview ......................99 Read/Write Internal Memory ................. 99 Read Internal Memory ......................99 Write Internal Memory ....................... 103 Function Block ..................... 107 GET function block ......................107 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 11
TROUBLESHOOTING ............... 195 Error Code ....................195 Troubleshooting ..................197 Troubleshooting Sequence ................ 198 RDY LED OFF ........................198 RDY LED Blinks ......................... 199 Counter Operation Error ..................... 201 R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 12
GM Function Block Conversion Program ..........213 Preset value setting Function Block of GN (HSCC-PRE) ..........213 Preset value setting FB of 2MLI/2MLR ................213 Mode setting function block ....................215 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 13
Table 24 – Frequency Displayed Mode Setting ............83 Table 25 – Output Status Setting at PLC Stop .............. 83 Table 26 – Configuration of I/O signals of 2MLF-HO2A and 2MLF-HD2A ....85 Table 27 – Error Code ....................195 Table 28 –...
Page 14
Contents Figures Figures Figure 1 – Parts of 2MLF-HO2A/HD2A ................25 Figure 2 – Up/Down Count Operation by Program Setting ..........35 Figure 3 – Up/Down Count Operation by Program Setting ..........36 Figure 4 – Up/Down Count Operation by B-phase Input Signal ........36 Figure 5 –...
Page 15
Figure 81 – Present Value Recovery in case of Power Failure ........141 Figure 82 – 2MLK series system ................. 142 Figure 83 – 2MLI series system .................. 142 R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 16
Figure 123 – System Configuration ................179 Figure 124 – Assignment of I/O signal ................. 180 Figure 125 – Operation Type ..................180 Figure 126 – Operation Timing ..................181 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Two outputs are provided for each channel. 6. High Speed counter module has six additional functions: Count Clear Count Latch Sampling Counter Input Frequency Measure Revolution/Unit time Count Disable R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 20
1. Introduction 1.2. Functions 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Linear Count with Carry/Borrow when 32-bit range is exceeded, maximum/minimum count Count mode (program setting) Ring Count (repeated count within setting range) 1-phase input Input mode (program setting) 2-phase input CW/CCW input Signal type Voltage R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 22
Module Ready, A/B phase pulse input status To be set through program (count available only in Count Enable enable status) Preset function To be set through terminal or program 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Input current 7–11 mA 7–11 mA 7–11mA RS-422A Line Driver ON guaranteed 17.0 V 9.8V 4.1V voltage (minimum) HTL LEVEL OFF guaranteed 4.5V 3.0V 1.7V Line Driver voltage (maximum) R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Less than or equal to 0.1mA Saturated area voltage Less than or equal to 1.3V ON delayed time Less than or equal to 0.1ms OFF delayed time Less than or equal to 0.1ms 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
2. Specifications 2.2. Designations of Parts Designations of Parts 2MLF-HO2A/HD2A Figure 1 – Parts of 2MLF-HO2A/HD2A R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
2. Specifications 2.3. Specifications for Interface with External Devices Specifications for Interface with External Devices Arrangement of connector pins 2MLF-HO2A: The connector pin arrangement is displayed in Table 6. Table 6 – 2MLF-HO2A Connector Pin Arrangement Pin No. Pin arrangement...
Page 28
Gate DC24V input Gate COM terminal Gate DC5V input Compared output OUT1 OUT1 Compared output OUT0 OUT0 Supply TERMINAL of external power DC24V Supply TERMINAL of external power 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
5. The counter module also supports the following auxiliary modes: Count Clear Count Latch Sampling Count Input Frequency Measure Count Function of Input Revolution/Unit Time Count Disable Function Pulse Input Mode 1-Phase Input Mode 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Up/Down count classification A-Phase input pulse rising A-Phase input pulse falling Up/Down count setting signal Up count Up count Up/Down count setting signal ON Down count Down count R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
1-phase, 2-input, 2-multiplication operation mode: The counter counts A- − phase input pulses at the rising and falling edge The B-phase input pulse decides between up and down count operations. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Up/Down count classification A-phase input pulse Up count Up count precedes B B-phase input pulse Down count Down count precedes A Figure 7 – 2-Phase, 2-Multiplication Operation Mode 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
B-phase input pulse is Low with respect to A-phase input pulse. Down count operation is executed at the rising edge of B-phase pulse input, when A-phase input pulse is Low with respect to B-phase input. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Linear Count range: -2,147,483,648 – 2,147,483,647 Up count If count value reaches the maximum value while increasing, Carry occurs, and count stops and increasing is not available but decreasing is available. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
If count value reaches the minimum value while decreasing, Borrow occurs, and count stops and decreasing is not available but increasing is available. Figure 10 – Linear Count R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Figure 11 – Ring Count Down count − During down count mode, if count value reaches user-defined minimum value, Borrow occurs and count is executed starting from maximum value. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Figure 13 – Ring Count based on Present Count Value During down count, if count reaches minimum value, borrow occurs and count − is changed into ring count maximum value. Count is executed until R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Enable Preset to change the current count. 3. Operation method is as follows: Setting preset value -> Enable Preset On. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
1 (ON), when external preset detection is 1(ON), external preset is not executed. In order to change external preset detection as 0 (OFF), turn on external preset detection reset. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
2. Two separate compared outputs are available for each channel. 3. The seven output conditions are used for comparing present count value with compared value. The conditions are shown below. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
Value less than compared value, output is kept ON. In order to turn the output OFF, identical reset signal is to be ON. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 48
If present count value is greater than compared value, output is sent out, and if count value decreases to be less than or equal to compared value, output is not sent out. Count Value > Compared Value 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 49
Compared Enabled Signal must be ON (output is displayed only on program U device or Global variable), and in order to send out the actual external output, the Output-Enabled Signal must be ON. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
High Speed counter module provides six auxiliary modes, with basic count function and compared output function. 8. To use the auxiliary modes, Auxiliary Mode Enabled Signal must be ON. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
When auxiliary mode enabled signal is ON, present count value is latched. 11. Setting method: Set auxiliary mode setting mode to 2 and set Auxiliary Mode Enabled Signal ON. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Sampling Count Function is used to count from 0 for a specified time when • Auxiliary Mode Enabled Signal is ON. In other words, while Auxiliary Mode Enabled Signal is ON, operation is not continuous. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
While Auxiliary Mode Enabled Signal is ON, the counter measures the input • frequency per second (or set unit). Setting method: Set auxiliary mode setting mode to 4 and set Auxiliary Mode • Enabled Signal ON. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Auxiliary Mode Enabled Signal is ON. (Figure 18 shows the example of 1Hz unit of frequency-displayed mode selected.) Figure 18 – Input Frequency Measure 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
ON, it counts the number of input pulses for the unit time with auxiliary mode in progress. (Figure 19 shows the example where the number of pulses per revolution is Figure 19 – Revolution/Unit Time R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Auxiliary Mode Enabled Signal ON. Display during auxiliary mode operation: While Auxiliary Mode Enabled Signal is ON, count operation stops, with auxiliary mode in progress. Figure 20 – Count Disable 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
25. Do not let any foreign materials like wiring waste inside the casing at the top of the module during wiring. Get rid of foreign materials if any. 26. Do not install or remove the module while the power is ON. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
31. The wiring is identical if the pulse generator of voltage output type is used through Totem Pole output. 32. Wiring of the preset signal is identical to the gate signal. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
This is the wiring example which it used the pulse generator (Encoder or Manual pulse generator) of NPN Open Collector output type. Figure 22 – Example of DC24V NPN Open Collector Output Wiring 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
This is the wiring example which it used the pulse generator (Encoder or Manual pulse generator) of PNP Open Collector output type. Figure 23 – Example of DC24V PNP Open Collector Output Wiring R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
RS-422A Line Driver (5V level) output type. Figure 24 – Example of Line Driver Output Wiring ATTENTION In case of 24V Level Line Driver, you must connect to AII+, AII-, BII+, BII- terminal. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Figure 26. 35. Type the name of the project in Project name box (Ex: 2MLF-HO2A) and enter the path and a folder name in File directory box, and then click OK.
4. Operating Procedures and Monitoring 4.2. Operation Method Figure 26 – Project Window 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 65
Once a project is created, click Online > Connection Settings or on the toolbar, click to specify the connection method and connection stage, and then click Settings to specify the communication port as shown in Figure 30. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Figure 27 – Setting Communication Ports After all settings are completed, click Online > Connect or click on the tool bar. Click Message Window > Communication to check the connection status. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Click module area of the applicable slot to select the applicable module. Double-click the corresponding slot to specify the parameters, or click Details to display the screen where parameters can be set. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
4. Operating Procedures and Monitoring 4.3. Parameters Setting Step Action Figure 30 – Parameter Setting Window (1) On the parameters setting window, set parameters as necessary for the operation. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Action Figure 31 – Parameter Setting Window (2) ATTENTION You must make the scan program to change parameter of the high speed counter module during CPU RUN mode. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Figure 32. Figure 32 – Special Module Monitoring On the module list dialog box, current modules of PLC system are displayed. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
In the lower portion parameter items of each module can be changed individually. If you click Test button, setting values is applied to current value. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
If PLC CPU module is STOP mode, it is available to test operation and monitoring function. However, in case of RUN mode, it is available only to monitoring function. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 74
Step Action To monitor the I/O contact status, click appropriate channel’s flag monitoring area to display the monitoring screen. Here contact status of each I/O can be checked. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
SoftMaster Project of 2MLI series View Global/Direct variables On Project Window, select View > Variables. Currently registered variables and comments are displayed. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Select Edit > Register Special Module variable to register special module variable. First, Global/Direct Variables window has to be executed. A message box appears as shown below. Figure 37 – Register Special Module Variable (1) R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
4.5. Register Special Module Variables Click Yes to complete the Special Module variable registration that is set in I/O parameter setting. Figure 38 – Register Special Module Variable (2) 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
2147483648 Select OUT0 type 0 ~ 6 Select OUT1 type 0 ~ 6 OUT0 compared based value (single- -2147483648~ compared)/minimu 2147483648 m setting value (section compared) R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 80
Revolutions per 0 ~ 60000 hour count time setting Revolutions per hour function, 0 ~ 3 pulses per revolution input Select frequency 0 or 1 displayed mode 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
OUT is ON If compared value1 =< present value =< compared value2, OUT is ON If compared value1 >= present value, present value >= compared value2, OUT is ON 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Output status setting when PLC is in stop state (CH0, CH1 common: 32H) Table 25 – Output Status Setting at PLC Stop Setting value (Dec) Details Output disable Output kept as it is R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
5.2. I/O Signals I/O Signals Configuration of I/O signals Configuration of I/O signals of 2MLF-HO2A and 2MLF-HD2A are as follows. Table 26 – Configuration of I/O signals of 2MLF-HO2A and 2MLF-HD2A PLC ≤ High Speed Counter PLC ≥ High Speed Counter...
Data Constant Value Value _Fxy_CH _Fxy_ Select counter 0_CNT_ CH1_C type 0 or 1 MODE NT_M _Fxy_CH _Fxy_ Select pulse 0_PLS_M CH1_P input type 0 ~ 7 LS_M R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 90
-2147483648 ~ P0_MA maximum setting 2147483647 value (section- compared) _Fxy_CH _Fxy_ OUT1 compared 0_CP1_M CH1_C based value -2147483648 ~ P1_MI (single- 2147483647 compared)/minim um setting value (section- 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 91
Constant value cannot be modified, because it is the address of input data area. • Constant value is the same as the internal memory address of 2MLK series. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
_Fxy_ERR_CODE Error code GET_### (channel 0, channel 1 common) Details and Data Configuration Count types (channel 0: _Fxy_CH0_CNT_MODE, channel 1: _Fxy_CH1_CNT_MODE) Setting value Contents Linear count Ring count 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 93
In case of comparison minimum value ≤ current count value ≤ comparison maximum value, OUT(1) is On In case of comparison minimum value ≥ current count value, current count value ≤ comparison maximum value, OUT(1) is On R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 94
100Hz 1000Hz(=1kHz) The status of comparison output during operation mode of 2MLI CPU module is stop mode.(channel 0, channel 1: _Fxy_PLCSTOP_OUT_EN) Setting value Contents Output disable Ouput preservation 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Additional function _xy_CH0_BRW Borrow detection _xy_CH0_AUXEN enable(level/edge) In operation of Comparison enable _xy_CH0_AUXING _xy_CH0_CMPEN additional function (level) _xy_CH0_CMPOUT The status of Comparison output _xy_CH0_OUTEN comparison output 0 enable (level) R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 96
_xy_CH1_CMPOUT The status of Comparison output _xy_CH1_OUTEN comparison output 0 enable (level) Equal (=) reset of _xy_CH1_CMPOUT The status of _xy_CH1_EQ0RST comparison output 0 comparison output 1 (edge) 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 97
1 (edge) _xy_CH1_CRTBRW Carry/Borrow reset _RST (edge) _xy_CH1_EXTPST External preset selection (edge) Selection of external _xy_CH1_EXTAUX additional function (edge) _xy_CH1_EXTPST Detection reset of _RST external preset(edge) R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 98
6. Global Constant and Global Variable 6.3. Global Variable 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Operation of GET/GETP Instruction Level Always executed with execution condition On GETP Executed with execution condition of operation start Configuration of GET/GETP Instruction Figure 40 – Configuration of GET/GETP Instruction R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Start address of the device to save the read data Number of words of the data to be read Integer Setting Base and Slot Number Figure 41 – Basic base 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
HSC module is installed at slot 8 of basic base and While M00000 is ON, it transmits the data (data1, data2) of internal memory 5 and 6 to D00015 and D00016. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 102
2MLK CPU module HSC module D area Internal memory data D00001 Data 1 D00002 Data 2 D00003 data 3 D00004 Data 4 D00005 Data 5 D00006 Data 6 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Start address of device integer with saved data to write M, P, K, L, T, C, D, #D Number of words of data to be written Integer Setting base and slot number R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
For ‘MADDR’, Global constant or integer is available. • ‘Output data’ is data read from Global constant. • In case of 2MLR, HSC module should be equipped at extension base. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 108
2MlI/2MLR CPU HSC module module Input variable (MADDR) Output variable Global variable Constant Data (DATA) value Output data1 _F08_CH0_CNT_MODE Data1 Note: Results of above two examples are same. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 109
‘_F24_CH1_CP0 _MIN’ to ‘OutputData2’. XGI/XGR CPU HSC module module Input variable (MADDR) Output variable Global constant Constant Data (DATA) value OutputData2 _F24_CH1_CP0_MIN Data2 R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
For ‘MADDR’, Global constant or integer is available. • ‘Output data’ is data read from Global constant. • In case of 2MLR, HSC module should be equipped at extension base. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 111
2MLI /2MLR CPU module HSC module Input variable (MADDR) Input variable Data Constant (DATA) Global constant value Data1 InputData1 _F0A_CH0_CNT_MODE Note: Operations of above two examples are same. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 112
(Data2) of ‘InputData2’ to ‘_F16_CH0_PRESET’. 2MLI/2MLR CPU module HSC module Input variable (MADDR) Input variable Data Constant (DATA) Global constant value Data2 Input data2 _F16_CH0_PRESET 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
(I/O Parameters > Parameters setting).Here the parameter-setting screen is used for writing the ring count maximum value and the ring count minimum value together on the internal memory of the High Speed counter module. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Write the above parameters and then the scan program on the PLC. (Input: A/B phase). The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
Operation Mode Setting These are the following options for Operation Mode Setting. The default mode is 2- phase, 1-multiplication. 2-phase, 1-multiplication • 2-phase, 2-multiplication • 2-phase, 4-multiplication • R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
The following figure shows the parameter-setting screen to write 2-phase, 4- multiplication on the internal memory of High Speed counter module. [I/O Parameters > Module Register (I/O Parameters setting)]. Figure 52 – Parameter Setting Screen 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Figure 53 – Ladder Program Write the above parameters and ladder program on PLC. The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.4. Basic Program Figure 54 – Use of Scan Program to set I/O parameters 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Since Preset Enabled Signal is set through I/O instruction area, the setting method of %U area address can be used. The following example is used to set the preset value to 10000. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Figure 57 – Ladder Program to set the Preset Enabled Signal The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 121
7. Programming 7.4. Basic Program R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
1000. Compared output is 0 respectively for the channel 0 and 1. Figure 61 shows the example of the scan program with compared value and condition specified, and compared output operation enabled. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. Figure 61 – Usage of Scan Program for Setting Compared Output 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Figure 65 shows the example of the scan program with Auxiliary Mode set to 1 (count clear) and Auxiliary Mode operation enabled. Figure 63 – Parameter Setting Screen for Auxiliary Mode1 R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
(gate input) of High Speed counter, to clear the counter. Figure 64 – Ladder Program for Auxiliary Mode Setting The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Figure 68 shows an example of the scan program with Auxiliary Mode set to 2 (Count Latch), Auxiliary Mode operation enabled, and then present latch count value is read. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7.4. Basic Program Figure 67 – Ladder Program for Auxiliary Mode2 The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Figure 71 shows an example of the scan program with Auxiliary Mode set to 3 (Sampling Count), additional function operation enabled and then present section count value read. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. Figure 71 – Scan Program for Auxiliary Mode Setting 3 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Figure 74 shows an example of the scan program with Auxiliary Mode set to 4 (Input Frequency Measure), Auxiliary Mode operation enabled and then present input frequency value read. Figure 72 – Parameter Setting Screen for Input Frequency Measure R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7.4. Basic Program Figure 73 – Ladder Program for Input Frequency Measure The alternative method for parameter setting is the usage of Scan program using PUTP instructions, as shown below. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Section setting value can be also specified, which the value per unit time is used for measuring revolutions per unit time. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
The following figure shows an example of the scan program with Auxiliary Mode set to 5 (Revolution/Unit time); Auxiliary Mode operation enabled, and then present revolutions per unit time value read. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
Figure 77 – Scan Program with Auxiliary Mode Set to 5 (Revolution/Unit time) Count Disable: Figure 79 shows the example of setting Auxiliary Mode to 6 (Count Disable) through I/O Parameters. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Figure 79 shows an example of the scan program with Auxiliary Mode set to 6 (Count Disable), Auxiliary Mode operation enabled and then present count value read. Figure 78 – Parameter Setting Screen for Count Disable 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The following figure shows the example of the scan program with Auxiliary Mode set to 6 (Count Disable); Auxiliary Mode operation enabled, and then present count value read. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
%K area (latch address) and presetting the previous count value to the present count value. Figure 81 – Present Value Recovery in case of Power Failure R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
1: Ring counter 1: Ring counter Ring counter min. Ring counter 100000 100000 max. Program Scan program of 2MLK series Figure 85 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Scan program of2MLI/2MLR series Figure 86 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 145
Integer can be inserted into ‘MADDR’ instead of global constant. The operation of the following program is same with that of the front example. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 146
7. Programming 7.6. Program • For integer corresponding to global constant, refer to Chapter 6. • On the next program example, scan program example using integer (constant) is omitted. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The following program example shows the setting pulse input mode. Setting contents Parameter Pulse input mode 3: CW/CCW 3: CW/CCW Program Scan program of 2MLK series Figure 87 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Scan program of 2MLI/2MLR series Figure 88 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The following program example shows how to checking current counter and operation by auxiliary function. Program Scan program of 2MLK series Figure 89 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Figure 90 – Scan program of 2MLI/2MLR series ATTENTION In Scan program of 2MLI/2MLR, the number of cell is changed by using icon or ‘Change Columns’ of ‘View’.. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The following program example explains about how to set preset value and enable preset. Setting content Parameter Preset value 1000 1000 Program Scan program of 2MLK series Figure 91 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Figure 92 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The following program example explains how to execute Enable counter. Program Scan program of 2MLK series Figure 93 – Scan program of 2MLK series Scan program of 2MLI/2MLR series Figure 94 – Scan program of 2MLI/2MLR series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
The following program example shows how to reset the detected carry/borrow signal. Program Scan program of 2MLK series Figure 95 – Scan program of 2MLK series Scan program of 2MLI/2MLR series Figure 96 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
When auxiliary function is ON, change the current counter as 0. Setting contents Parameter Auxiliary mode 1: Counter Clear 1: Counter Clear Program Scan program of 2MLK series Figure 97 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Scan program of 2MLI/2MLR Figure 98 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Setting content Parameter 3: Sampling 3: Sampling Auxiliary mode Count Count Range value 5000 5000 Program Scan program of 2MLK series Figure 99 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Scan program of 2MLI/2MLR series Figure 100 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
4: Input Freq. measure 4: Input Freq. measure Frequency Mode 1: 10Hz 1: 10Hz Program Scan program of 2MLK series Figure 101 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Scan program of 2MLI/2MLR series Figure 102 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
5: Revolution/Unit time Range value 1000 1000 Pulse/Rev value Program Scan program of 2MLK series Figure 103 – Scan program of 2MLK series Scan program of 2MLI/2MLR series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Figure 104 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
While Enable auxiliary is on, counting is not executed. Setting contents Parameter Auxiliary mode 6: Count Disable 6: Count Disable Program Scan program of 2MLK series Figure 105 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Scan program of 2MLI/2MLR series Figure 106 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The following program examples allows you to Enable preset by external preset signal and executing reset when external preset signal is detected. Program Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Figure 109 – Scan program of 2MLK series Scan program of 2MLI/2MLR series Figure 110 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Program Scan program of 2MLK series Figure 111 – Scan program of 2MLK series Scan program of 2MLI/2MLR series Figure 112 – Scan program of 2MLI/2MLR series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Figure 113 – Scan program of 2MLK series Scan program of 2MLI/2MLR series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Figure 114 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
The following program example explains how to execute Enable comparison, Enable comparison output, Comparison agreement reset. Program Scan program of 2MLK series Figure 115 – Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Scan program of 2MLI/2MLR series Figure 116 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Comparison output status when XGT CPU module is 1: Hold comparison output STOP Program Scan program of 2MLK series Figure 117 – Scan program of 2MLK series Scan program of 2MLI/2MLR series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
The following program example explains how to check error status and error code occurred at HSC module. Program Scan program of 2MLK series Figure 119 – Scan program of 2MLK series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
To prepare when PLC power is off, current count is saved every scan and if PLC power restart, preset operation is executed with the saved count. Program Scan program of 2MLK series R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.6. Program Figure 121 – Scan program of 2MLK series Scan program of 2MLI/2MLR series Figure 122 – Scan program of 2MLI/2MLR series 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 177
‘CH1 current count’ when PLC power is off, the following setting is necessary. On Basic Parameter, set Restart Method as Warm Restart. b) On scan program, set ‘CH0 current count’ and ‘CH1 current count’ as Retain variable. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 178
7. Programming 7.6. Program 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
2nd stop position and stops. When the 2nd Work Complete Signal is ON, it moves the object car back to the start position by means of reverse rotation. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Figure 125 – Operation Type *1: The difference of 100 between stop position and decelerated position is the delayed stop distance by the decelerated timed of the inverter. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
7. Programming 7.7. Application Program Program through I/O Parameter Setting) Module installation information setting Figure 127 – Module Installation Information Setting I/O assigned information setting 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
7. Programming 7.7. Application Program Figure 130 – Ladder Program for object car control R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
7. Programming 7.7. Application Program Program (through PUT/GET) Figure 131 – Ladder Program 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
If the start switch is pressed, drilling stops after rotation up to the specified degree (60°). If Drilling Complete signal is ON, drilling of another 60°is executed. After drilling operation is repeated 6 times, the process is completed. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
Compared output 0, minimum output value – 1,000 Pulses/1 revolution 360˚: So the number of pulses for 60˚rotation is X= (60*1000)/360=166 (Pulses when rotated 60 ˚: 166). 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
7. Programming 7.7. Application Program Program (through PUT/GET) Figure 139 – Ladder Program 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Compared output 0 maximum value exceeded maximum input range Compared output 0 minimum value > compared output 0 maximum value set Compared output 1 minimum value exceeded maximum input range R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 196
In case of non-fatal error where LED blinks every 1 sec, the parameter value causing the specific error is not set on the module, and the existing parameter value is kept as it is. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
Troubleshooting operation status sequence. Output operation is not See Figure 145 available Output operation is not Output Operation Error See Figure 146 consistent with operation status. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
8. Troubleshooting 8.3. Troubleshooting Sequence Troubleshooting Sequence RDY LED OFF Figure 140 – RDY LED OFF 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Counter type range exceeded Set counter type to (0-7) Pulse input type range exceeded Set pulse input type to (0-1) Auxiliary Mode type range exceeded Set Auxiliary Mode type to (0-6) R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 200
Auxiliary Mode type selected is revolutions per hour measurement) Set frequency input mode to (0-3). (Only if Frequency input mode range exceeded Auxiliary Mode type selected is input frequency measurement ) 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
OS version: shows the O/S version information of HSC module. OS date: shows the O/S prepared date of HSC module. Module status: shows the present error code. (Refer to Table 27). 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Z phase: 1 pulse is output for 1 revolution of shaft. That is, they are used to reset external counter or to detect the origin position. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
The counter value increases from -2,147,483,648 to 2,147,483,647 (for 32-bit counter). Figure 148 – Increasing Counter Decreasing Counter The counter value decreases from 2,147,483,647 to -2,147,483,648 (for 32-bit counter). Figure 149 – Decreasing Encounter 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Carry Signal generated when Linear count changes from 2,147,483,646 to 2,147,483,647 and when Ring count changes from the maximum value to the minimum value during increasing count operation. R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Signal generated when Linear count changes from -2,147,483,648 to 2,147,483,647 and when Ring count changes from the minimum value to the maximum value during decreasing count operation. Figure 152 – Borrow 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
External Preset External signal used to change present counter value to discretionarily specified value. External Gate External signal used to enable the additional function operation R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Rising edge) Base Number Base number where HSC module is BASE USINT equipped Input Slot Number Slot number where HSC module is SLOT USINT equipped USINT MADD Chann _F01_CH0_PRESE R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 214
If it is error status, it does not operate. In case of 2MLR CPU, HSC module should be equipped at extension base. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Base number where HSC module is BASE USINT equipped Slot Number Slot number where HSC module is SLOT USINT equipped Input Chann BOOL Linear count Ring count CNT_ Count BOOL type MODE R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 216
Since 2MLI/2MLR cannot process Mode setting Function Block (HSCC_MOD) at once like GM, it combines methods such as count type, pulse input type, Ring upper/lower count to execute function block. 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell...
Page 217
Base number where HSC module BASE USINT is equipped Slot Number Slot number where HSC module SLOT USINT is equipped Input _Fxy_CH0_PLS_MODE MADD Chann UINT _Fxy_CH1_PLS_MODE DATA DWORD 2phase 1multiplication Pulse R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 218
Slot Number Slot number where HSC module SLOT USINT Input is equipped _Fxy_CH0_RING_MIN Channe MADDR UINT _Fxy_CH1_RING_MIN Ring Count DATA DWORD -2,147,483,648 ~ 2,147,483,647 lower limit 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 219
If it completes, it outputs 1 and holds. If DONE BOOL Execution status error occurs, it outputs 0 Output STAT USINT Error status In case of error, outputs error code R200 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide May 2010 Honeywell...
Page 220
9. Appendix 9.3. GM Function Block Conversion Program 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 221
9. Appendix 9.3. GM Function Block Conversion Program 2MLF-HO2A, 2MLF-HD2A High Speed Counter Module User's Guide R200 Honeywell May 2010...
Page 222