3.6.7

Automatic initialization (structograms)

Linear actuator
Up
Figure 3-23
Direction of action of the actuators
SIPART PS2 Manual
A5E00074631-01
4.
Switch to the second parameter by pressing the operation mode
key
briefly.
Display:
NOTE
Make sure that the transmission ratio selector is in position 90 °!
5.
Switch on to the following display by pressing the operation mode
key
twice:
The following steps are identical with the steps 6) to 9) for initiali-
zation of linear actuators.
After successful initialization the determined rotary range appears
in the top display.
"5.INITM" appears in the bottom line again after pressing the ope-
ration mode key
tion operating mode.
To exit the Configuration mode, press the operation mode key
for longer than 5 seconds. The software version is displayed after
about 5 seconds. The instrument is in manual operation after re-
leasing the operation mode key.
Down
The initialization procedure should be taken from the following structo-
gram (figure 3-24 to figure 3-27). The terms Open/Closed and up/down
in the structogram refer to the direction of action of the actuators as
illustrated in figure 3-23.
briefly. This brings you back to the Configura-
Rotary actuator
Closed
Preparing for Operation
Open
67