Preparing for Operation
.
62
5.
Switch on to the following display
mode key twice:
6.
Start initialization by pressing the increment key
than 5 s.
Display:
7.
After 5 s the display changes to:
(The display of the potentiometer setting is shown here and below
as an example only).
Now move the actuator to the position which you want to define as
the first of the two end positions with the increment
ment
key. Then press the operation mode key
the current position as end position 1 and switches on to the next
position.
NOTE
If the message "RANGE" appears in the bottom line, the selected end
position is outside the permissible measuring range. There are several
ways to correct the error:
S Adjust the slip clutch until "OK" appears and press the operation mode
key again or
S move to another end position with the increment and decrement key
or
S abort initialization by pressing the operation mode key. You then have
to change to P manual operation and correct the displacement path
and the displacement detection according to step 1.
by pressing the operation
for longer
and decre-
. This accepts
SIPART PS2 Manual
A5E00074631-01