Software (Sw); Sw Version - Panasonic 1735 Technical Description

Alert annunciation units
Hide thumbs Also See for 1735:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
11
11.1
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x

Software (SW)

The software is stored in a flash memory in each AA unit. This
software can be replaced / updated (i.e. downloaded via Win512 /
Win128 / Win512 G3). All units connected to the same RS485 line
have to have the same SW version and it is highly recommended to
have the same SW version in all the display units in the system.

SW version

The SW version can be presented as follows:
1 Do the same as by SW mode and address setting, see chapter
"SW mode setting", page 16.
2 When the following is displayed:
MODE SETTING!
Type: xxxxxxxxxxxx
....press push button "P2" (yellow) and the following will be
displayed:
ADDRESS SETTING
Address: XX
....press push buttons "P1" (black) and "P2" (yellow)
simultaneously and the following will be displayed:
Rst: nn
Addr: aaaaaaaa
Return = Yellow
nn = restart type (code) and
before restart.
nn=00:
Power On Reset. (Power supply connected)
nn=01:
Watchdog Reset.
nn=02:
Accidental jump to reset vector.
nn=03:
External reset caused by external watchdog/user
(e.g. after SSD download) or jumper "JP1"
(RESET) has been used.
nn=4-19:
Unexpected interrupt.
If nn=01, 02 or 04-19 appear often, call for service personnel /
engineer.
V.vvvv = SW version (e.g. 1.4.x).
3 Press yellow push button ("P2") – or see 6 below – and the
following will be displayed:
ADDRESS SETTING
Address: XX
4 Press
yellow
push button ("P2").
Change = Black
Store = Yellow
Change = Black
Store = Yellow
Version: V.vvvv
Erase SSD = Black
aaaaaaaa
= memory address
Change = Black
Store = Yellow
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

1736

Table of Contents