Panasonic Electric Works Nordic AB
MEW01295 Rev: 2
10.2.2
10.2.3
Technical Description Alert Annunciation Units 1735 & 1736, ver. 1.4.x
System EBL128
"FAULT:
No reply AAU x.
The contact with the AA unit is interrupted. Check the cable
and all connections. Is a correct / complete SSD download (via
Win128) performed? Check the address setting, SW mode
setting, etc. See also chapter "Restart", page 23.
"FAULT:
AAU x "
The AA unit is programmed (via Win128) as another type of
unit or there is a fault in the AA unit.
"FAULT:
Site specific data (SSD), AAU x.
See chapter "Restart", page 23.
System EBL512 G3
"
FAULT:
No
reply,
control unit xx
The contact with the ext. AAU is interrupted. Check the cable
and all connections. Is a correct / complete SSD download (via
Win512 G3) performed? Check the address setting, SW mode
setting, etc. See also chapter "Restart", page 23.
"FAULT:
Alert annuniciation unit xx"
The AAU is programmed (via Win512 G3) as another type of
unit or there is a fault in the AAU.
"FAULT: External presentation unit xx, control unit
xx"
The AAU is programmed (via Win512 G3) as another type of
unit or there is a fault in the AAU.
"FAULT:
Site
specific
unit xx, control unit xx.
See chapter "Restart", page 23.
alert
annunciation
data,
alert
26
unit
xx,
annunciation