Water System Venting; Draining The Water System; Water Quality Recommendations; Ventilation Requirements - Sullair TS32 Series User Manual

Industrial rotary screw air compressor, 200-350hp/149-261kw air-cooled & water-cooled standard and 24kt
Hide thumbs Also See for TS32 Series:
Table of Contents

Advertisement

SECTION 4
Table 4-2: Ventilation Requirements
MOTOR
MODEL
HP/KW
TS32-200
200/150
TS32-250
250/187
TS32-300
300/225
TS32-350
350/260
(I) Applicable to air-cooled models only.
(II) Applicable to compressors with enclosure.
NOTE
The required flow rate depends upon the
cooling water's temperature before it
enters the cooling system. The higher the
initial temperature, the higher the
required flow rate: the lower the initial
temperature, the lower the required flow
rate.
W
S
V
ATER
YSTEM
ENTING
Vent the system after installation, or after draining
the system at startup:
1. Open the water valve(s).
2. Open the vent cocks (located on top of the
aftercooler and lubricant cooler on the water
side) and let air escape from the system.
Close the vent cocks when water is visible at
their location - at this point the system has
been vented.
D
W
RAINING THE
ATER
To drain the system completely:
WATER COOLED OR REMOTE
COOLED COMPRESSOR
PACKAGE
HEAT REJECTION
BTU/HR
FLOW (II)
47,620
57,360
64,170
74,320
S
YSTEM
AIR-COOLED (I) COOLING PACKAGE
VENT
FAN
HEAT REJECTION
BTU/HR
CFM
4150
560,200
4150
674,800
4150
802,100
4150
929,000
1. Disconnect both the inlets and discharge
water lines located at the rear of the com-
pressor.
2. Remove the drain plugs that are located at
the bottom of the aftercooler and the lubri-
cant cooler end caps.
3. Allow the system to drain completely.
W
Q
ATER
UALITY
Water quality can significantly effect the efficiency of
the water cooling system. Dissolved minerals, gases,
and pH values are factors that contribute to the
formation of deposits and corrosion which can form
on the interior of cooling system pipes and heat
exchangers.
Scale can be a problem if the water supply has a
high concentration of calcium carbonate. It forms
lime scale deposits which act as thermal insulators
and restrict the water flow through the cooling
system. If scale is allowed to build up over time, it will
reduce the system's ability to remove heat and the
compressor can be damaged. Scale buildup can be
controlled with proper water treatment.
A thin lime scale coating is desirable and can inhibit
corrosion.
TS32 USER MANUAL
AIR FLOW CFM
18,000
18,000
28,000
31,000
R
ECOMMENDATIONS
57