Johnson Controls METASYS TC-9102 Series Technical Bulletin page 6

Fan coil unit controller with room command module

Advertisement

Standalone
Mode
WINDOW CONTACT
WINDOW OPEN
WINDOW CLOSED
Supervisory
Mode
WINDOW
SUPERVISORY
CONTACT
MODE
OPEN
ANY MODE
OFF
NIGHT
STANDBY
CLOSED
COMFORT
OFF/MANUAL
NIGHT/MANUAL
STANDBY/MANUAL
COMFORT/MANUAL
6
Technical Bulletin—TC-9102
The controller operates in standalone mode when it is not connected to a
supervisory system via the communications bus nor to a TM-9180 Room
Command Module. In standalone mode the controller may operate in one
of three control modes:
• COMFORT (occupied): control at comfort set point
• STANDBY (unoccupied): control at a standby level set point
• OFF (not in use): low limit control only
The control modes are set by the window contact and occupancy sensor
inputs, and may be modified by the occupancy button on the Room
Command Module as shown in Table 1.
Table 1: Standalone Modes
OCCUPANCY SENSOR
NO ACTION
OCCUPIED
UNOCCUPIED
When connected to a supervisory system via the communications bus or
to a TM-9180 Room Command Module, the controller may operate in
COMFORT, STANDBY or OFF control modes, and additionally in
NIGHT mode:
NIGHT (scheduled unoccupied): control at a night level set point.
The control modes are set by the supervisory system or TM-9180, and are
modified by the occupancy sensor input and occupancy button on the
Room Command Module as shown in Table 2. The window contact input
always switches the controller to OFF control mode, and a MANUAL
mode is available from the supervisory system to inhibit the action of the
occupancy sensor and occupancy button.
Table 2: Supervisory Modes
OCCUPANCY
SENSOR
NO ACTION
OCCUPIED
UNOCCUPIED
OCCUPIED
UNOCCUPIED
OCCUPIED
UNOCCUPIED
OCCUPIED
UNOCCUPIED
NO ACTION
CONTROL MODE
OFF
COMFORT
STANDBY
CONTROL MODE
OFF
OFF
OFF
NIGHT
NIGHT
STANDBY
STANDBY
COMFORT
STANDBY
OFF
NIGHT
STANDBY
COMFORT
*(T) = Timed (Returns to Control Mode after 1 hour.)
ALTERNATE MODE
(OCCUPANCY BUTTON)
NO ACTION
STANDBY
COMFORT
ALTERNATE MODE
(OCCUPANCY BUTTON)
NO ACTION
OFF
OFF
COMFORT (T)*
COMFORT (T)*
COMFORT
COMFORT (T)*
STANDBY
COMFORT
NO ACTION