Johnson Controls METASYS TC-9102 Series Technical Bulletin page 29

Fan coil unit controller with room command module

Advertisement

Parameters for
Supervisory
System
Parameter Description
Room Temperature
Remote Set Point
Working Set Point Heating
Working Set Point Cooling
Control Output Heating
Control Output Cooling
Heating/Cooling Mode
Operating Status
Alternate Mode
Window Contact
Occupancy Sensor
Low Limit Mode
Winter Set Point Compensation
Summer Set Point Compensation
Requested Operating Mode
Set Outdoor Temperature
Set Common Set Point
On/Off Fan Control:
Fan Status
3-Speed Fan Control:
Fan Speed 1
Fan Speed 2
Fan Speed 3
Fan Override
Fan Speed Controller:
Control Output Fan
The following table lists the parameters which are available for
monitoring by Metasys supervisory systems. For details of configuration
procedures and override possibilities, refer to the technical documentation
of the system which is to be used.
Table 4: Supervisory System Parameters
*Note: For 0-10 VDC control signal outputs, OCM1 and OCM2 operate
in parallel and indicate the output level in Heating or Cooling.
Therefore, at the supervisory system, OCM1 should be monitored
as the "Heating/Cooling Control Output" and L1A can be
monitored to indicate whether the controller is in heating or
cooling mode. (Requires Metasys Release 9.0 or later.)
Units
°C
°C or K
°C
°C
%
%
Cool/Heat
Comfort/Standby/Night/Off
Off/On
Closed/Open
Occupied/Unoccupied
Off/On
K
K
Comfort/Standby/Night/Off
°C
°C or K
Off/On
Off/On
Off/On
Off/On
Auto/Hold
%
Tag Name
AI1
Read
AI2
Read
WSP1
Read
WSP2
Read
OCM1
Read
OCM2*
Read
L1A*
Read
MODS
Read
ALT
Read
WIN
Read
OCC
Read
AFM
Read
WAC
Read
SAC
Read
MODC
Write
XAI4
Read/Write
PM6K1
Read/Write
DO2
Read
DO5
Read
DO6
Read
DO7
Read
FOV
Read
OCM3
Read
Technical Bulletin—TC-9102
Function
29

Advertisement

loading

This manual is also suitable for:

Metasys tm-9100 seriesMetasys tm-9150Metasys tc-9102Metasys tm-9160Metasys tm-9180