Gas Valve; Inlet Gas Pressure Range; Nominal Manifold Pressure - York FC9C UP Series Installation Manual

High efficiency tubular heat exchanger series. (modulating upflow with ecm motor) 60 - 120 mbh input (17.6 - 35.2 kw) input
Table of Contents

Advertisement

292278-UIM-A-0108
Be sure to relight any gas appliances that were turned off at the
start of this input check.
TABLE 13: Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas
Minimum
4.5" W.C. (1.12 kPa)
Maximum
10.5" W.C. (2.61 kPa)
IMPORTANT: The inlet gas pressure operating range table specifies
what the minimum and maximum gas line pressures must be for the fur-
nace to operate safely.
The gas line pressure MUST BE
• 7" W.C. (1.74 kPA) for Natural Gas
• 11" W.C. (2.74 kPA) for Propane (LP) Gas
in order to obtain the BTU input specified on the rating plate and/or the
nominal manifold pressure specified in these instructions and on the
rating plate.
ADJUSTMENT OF MANIFOLD GAS PRESSURE
Follow the appropriate section in the instructions below. Refer to Figure
23 for a drawing of the locations of the pressure ports on the gas valve.
Turn gas off at the ball valve or gas cock on gas supply line
before the gas valve.
1.
The manifold pressure must be taken at the port marked OUT
PRESS TAP.
2.
The inlet gas line pressure must be taken at the port marked IN
PRESS TAP.
3.
Using a 3/16" allen wrench, remove the plugs from the inlet and
outlet pressure ports. Connect a 1/8" UPT barbed hose fitting to
each pressure port.
Read the inlet gas pressure using the method below.
A.
Disconnect the pressure reference hose from the burner box.
Using a tee fitting and a short piece of hose, connect the neg-
ative side of the manometer to the burner box as described
below.
B.
Remove one end the 5/16" (7.94 mm) ID flexible tubing over
the pressure port on the burner box.
C.
Insert the end of the 5/16" (7.94 mm) tubing, that has the 1/8"
(3.175 mm) adapter at the end of the tube, in to the 1/8"
(3.175 mm) tee.
D.
Connect the 1/8" (3.175 mm) tee to the burner box adapter
and to the negative side of a U-tube manometer or digital
pressure measuring equipment with 2 – 1/8" (3.175 mm)
tubes.
E.
Use the 5/16" (7.94 mm x 1/8" (3.175 mm) reducing coupling
and a 4" (101.6 mm) piece of 1/8" (3.175 mm) tubing to con-
nect the positive side of the manometer to the gas valve pres-
sure reference port. Refer to Figure 24 for connection details.
IMPORTANT: The cap for the pressure regulator must be removed
entirely to gain access to the adjustment screw. Loosening or tightening
the cap does not adjust the flow of gas.
1.
Refer to Figure 23 for location of pressure regulator adjustment
cap and adjustment screws on main gas valve.
24
2.
3.
TABLE 14: Nominal Manifold Pressure
Propane (LP)
8.0" W.C. (1.99 kPa)
13.0" (3.24 kPa) W.C.
INLET
PRESSURE
TAP
FIGURE 23: Gas Valve
IMPORTANT: If gas valve regulator is turned in (clockwise), manifold
pressure is increased. If screw is turned out (counterclockwise), mani-
fold pressure will decrease.
4.
5.
6.
Turn gas and electrical supplies on and follow the operating
instructions to place the unit back in operation.
Adjust manifold pressure by adjusting gas valve regulator screw
for the appropriate gas per the following:

NOMINAL MANIFOLD PRESSURE

Natural Gas (Max)
Natural Gas (Min)
Propane (LP) Gas (Max)
Propane (LP) Gas (Min)
ON/OFF
KNOB
After the manifold pressure has been adjusted, re-calculate the
furnace input to make sure you have not exceeded the specified
input on the rating plate. Refer to "CALCULATING THE FURNACE
INPUT (NATURAL GAS)".
Once the correct BTU (kW) input has been established, turn the
gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing and fittings from the gas valve pressure
tap and the pressure reference hose from the burner box and
replace the pressure tap plugs. Replace the burner box front cover
(if it was removed) and place the pressure reference hose back on
the gas valve.
Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved gas detector, a non-corrosive
leak detection fluid, or other leak detection methods.
The manifold pressure must be checked with the screw-off cap for
the gas valve pressure regulator in place. If not, the manifold pres-
sure setting could result in an over-fire condition. A high manifold
pressure will cause an over-fire condition, which could cause pre-
mature heat exchanger failure. If the manifold pressure is too low,
sooting and eventual clogging of the heat exchanger could occur.
Be sure that gas valve regulator cap is in place and burner box to
gas valve pressure reference hose is connected.
3.5" w.c. (0.87 kPa)
0.6" w.c. (0.15 kPa)
10.0" w.c. (2.49 kPa)
1.6" w.c. (0.40 kPa)