TABLE 7: Equivalent Length of Fittings
Fitting
2" 90º sweep elbow
2" 45º sweep elbow
2" 90º standard elbow
2" 45º standard elbow
3" 90º sweep elbow
3" 45º sweep elbow
3" 90º standard elbow
3" 45º standard elbow
2" corrugated connector
3" corrugated connector
Example:
An 80,000 BTUH furnace requires 32 feet of pipe and four 90º elbows.
Using 2" pipe and standard elbows, the total equivalent length will be:
32 feet of 2" pipe =
4 - 90º standard 2" elbows = (4x10) =
Total =
This exceeds the 65 foot maximum equivalent length of 2" pipe allowed
for that model and is thus not acceptable.
By using sweep elbows, the total equivalent length will be:
32 feet of 2" pipe =
4 - 90º standard 2" elbows = (4x5) =
Total =
This is less than the 65 foot maximum equivalent length of 2" pipe
allowed for that model and is thus acceptable.
Alternatively, using 3" pipe and standard elbows, the total equivalent
length will be:
32 feet of 3" pipe =
4 - 90º standard 2" elbows = (4x5) =
Total =
This is less than the 90 foot maximum equivalent length of 3" pipe
allowed for that model and is thus acceptable.
A
STANDARD ELBOW
FIGURE 11: Dimensions
TABLE 8: Elbow Dimensions
Elbow
"A" Dimension
2" Standard
2-5/16"
3" Standard
3-1/16"
2" Sweep
3-1/4"
3" Sweep
4-1/16"
Unitary Products Group
Equivalent Length
5 feet of 2" pipe
2-1/2 feet of 2" pipe
10 feet of 2" pipe
5 feet of 2" pipe
5 feet of 3" pipe
2-1/2 feet of 3" pipe
10 feet of 3" pipe
5 feet of 3" pipe
10 feet of 2" pipe
10 feet of 3" pipe
32 equivalent feet
40 equivalent feet
72 equivalent feet of 2" pipe
32 equivalent feet
20 equivalent feet
52 equivalent feet of 2" pipe
32 equivalent feet
40 equivalent feet
72 equivalent feet of 3" pipe
A
LONG (SWEEP) ELBOW
Dimensions are those required in Standard ASTM D-3311.
NOTE: Sidewall vent terminal may be used for sidewall vent termina-
tions. Refer to part list in the back of the USERS INFORMATION AND
SERVICE AND MAINTENANCE MANUAL for the terminal part number.
TABLE 9: Combustion Air Intake and Vent Connection Size at Furnace
(All Models)
FURNACE VENT CONNECTION SIZES
60 - 100 MBH
Furnace Input
(17.5 - 29.3 kW)
Intake Pipe Size
2" (5.1 cm)
Vent Pipe Size
2" (5.1 cm)
*. Vent pipe size must be increased to 3" diameter after connection to furnace
on this model.
IMPORTANT: Accessory concentric vent / intake termination kits
1CT0302 and 1CT0303 are available and approved for use with these
furnaces. Horizontal sidewall vent terminations kits 1HT0901 &
1HT0902 are also approved for use with these furnaces.
IMPORTANT: Furnace vent pipe connections are sized for 2" (5.1 cm).
pipe. Any pipe size change must be made outside the furnace casing in
a vertical pipe section to allow proper drainage of condensate. An offset
using two 45º (degree) elbows will be required for plenum clearance
when the vent is increased to 3" (7.6 cm).
COMBUSTION AIR AND VENT PIPING ASSEMBLY
The final assembly procedure for the combustion air and vent piping is
as follows:
1.
Cut piping to the proper length beginning at the furnace.
2.
Deburr the piping inside and outside.
3.
Chamfer (bevel) the outer edges of the piping.
4.
Dry-fit the vent piping assembly from the furnace to the outside ter-
mination checking for proper fit support and slope.
5.
Dry-fit the combustion air piping assembly checking for proper fit,
support and slope on the following systems:
A.
Sealed combustion air systems from the furnace to the out-
side termination.
B.
Ventilated combustion air systems from the furnace to the
attic or crawl space termination.
Solvent cements are flammable and must be used in well-ventilated
areas only. Keep them away from heat, sparks and open flames.
Do not breathe vapors and avoid contact with skin and eyes.
6.
Disassemble the combustion air and vent piping, apply cement
primer and the cement per the manufactures instructions. Primer
and cement must conform to ASTM D2564 for PVC, or ASTM
D2235 for ABS piping.
7.
All joints must provide a permanent airtight and watertight seal.
8.
Support the combustion air and vent piping such that it is angled a
minimum of 1/4" per foot (0.635 cm/m) so that condensate will flow
back towards the furnace. Piping should be supported with pipe
hangers to prevent sagging.
9.
Seal around the openings where the combustion air and / or vent
piping pass through the roof or sidewalls.
COMBUSTION AIR / VENT CLEARANCES
IMPORTANT: The vent must be installed with the following minimum
clearances, and must comply with local codes and requirements.
292278-UIM-A-0108
120 MBH
(35.2 kW)
3" (7.6 cm)
3" (7.6 cm)*
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fl9c up seriesPc9 up series

Table of Contents