Honeywell ControlEdge 900R04-0200 Getting Started page 90

Plc and rtu
Table of Contents

Advertisement

Chapter 6 - Communication
90
14.
Under Logical POUs, double-click the code worksheet
program that you have inserted. The workspace appears.
15.
Drag the target function or function block of modbus from the
Edit Wizard pane into the workspace, the function or function
block is displayed. There are twelve function blocks available for
Modbus master programming. For more details, see "Description
of Modbus Function Block" on page 1. For the following steps, the
function block MB_RD_MHR is taken as an example.
16.
Double-click the pin-outs of the function or function block to
assign variables. In the pop-up
the
,
Name
Data Type
Initial value and I/O address. Then click
To assign initial values to CONFIG_INFO:
CONFIG_INFO, a predefined data structure for Modbus
configuration information, is the crucial input for Modbus master
function blocks and contains key Modbus communication
parameters such as IP address of slave, slave ID, port number of the
controller to be used, etc. This data structure is read-only and
cannot be viewed and edited in RTU Builder. See "Description of
CONFIG_INFO" on page 1 for more details. Slave1 is the variable
name assigned by the user of CONFIG_INFO.
Variable Properties
and
from the drop-down list, and assign
Usage
OK
of the
window, select
.