Chapter 6 - Communication
98
1.
From the Home Page of ControlEdge Builder, click the arrow
beside
Configure Ethernet Ports
2.
Under
Network Setting
the IP address of the Ethernet port.
3.
Under
Protocol Binding
4.
Click
to complete the configuration.
Save
Configuring parameters for OPC UA Client
OPC UA client maintains sessions in response to each execution of
the UaConnect function block. One execution of the UaConnect
function block contains that one corresponding session will be
created by the OPC UA client on the controller and correspondingly
one session will be created on the target OPC UA server.
ATTENTION: Make sure that the OPC UA client's time is
synchronized to the controller's time.
To configure an OPC UA client
1.
Click
Configure Protocols
appears.
2.
Select the values for the
parameters. It is recommended to use the default
Per Session
values.
See the following table for the parameter description.
Parameter
Max Session
Count
Max
Subscriptions Per
Session
, and select
, select
Use the following IP address
, select
OPC UA Client
>
. The
OPC UA Client
Max Session Count
Description
The maximum number of concurrent sessions
allowed by the client.
If you enter a value of 0, the number of
sessions allowed is unlimited.
The default value is 100.
The maximum number of subscriptions
allowed by the client for one session.
If you enter a value of 0, the number of
subscriptions allowed is unlimited.
The default value is 10.
or
.
ETH1
ETH2
and enter
.
page
OPC UA Client
and
Max Subscription