Recorder Management - Siemens SENTRON PAC5200 Device Manual

Power monitoring device and power quality recorder
Table of Contents

Advertisement

14 Operating Parameters
14.4 Recording and Reporting
14.4.3

Recorder Management

Parameter
Average intervals - Frequency
Short term flicker
Long term flicker
Average interval - Voltage /
Unbalance / Harmonics
Record additional data (I, P, Q,
S etc.)
Recorder of average - Min
Recorder of average - Max
Harmonics parity
File generation every:
(corresponds to the setting of
the Average interval parame-
ter)
Recorded file type
Flicker lamp model
Tolerance unit
Tolerance number
Maximum recording interval
1)
The trend recorder also creates a PQDIF file when 1024 data points have been generated within the re-
cording interval.
254
Default Setting
Measurement Recorder
10 s
10 min
2 h
10 min
no
no
no
Odd
24 h
PQDIF
230 V
Trend Recorder
Percentage
Percentage: 3 % of declared
input voltage Udin,
Numerical: 0.50 V
10 min
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
Setting Range
fixed
fixed
fixed
30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
no
yes
no
yes
no
yes
Even
Odd
All
File generation
At average interval
every:
1 h
30 s
2 h
1 min
2 h
10 min, 15 min,
30 min, 1 h or
4 h
2 h
6 h
12 h
24 h
PQDIF
CSV
All
230 V
120 V
Percentage
Numerical
1 % to 5 % in 1 % steps
0.20 V to 500.0 V
10 min, 30 min, 1 h, 2 h, 4 h, 6 h,
1)
12 h, 24 h
E50417-H1040-C568-A1, Edition 03.2015

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron pac5100

Table of Contents