15 Operating Parameters
15.4 Recording and Reporting
15.4.3
Recorder Management
SICAM P850
Parameter
Average intervals - Frequency
Average interval - Voltage /
Unbalance / Harmonics
Record additional data (I, P, Q,
S etc.)
Recorder of average - Min
Recorder of average - Max
Harmonics parity
File generation every:
(corresponds to the setting of
the Average interval parame-
ter)
Recorded file type
SICAM P855
Parameter
Average intervals - Frequency
Short term flicker
Long term flicker
Average interval - Voltage /
Unbalance / Harmonics
Record additional data (I, P, Q,
S etc.)
296
Default Setting
Measurement Recorder
10 s
10 min
no
no
no
Odd
24 h
CSV
Default Setting
Measurement Recorder
10 s
10 min
2 h
10 min
no
Setting Range
fixed
30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
no
yes
no
yes
no
yes
Even
Odd
All
File generation
At average interval
every:
1 h
30 s
2 h
1 min
2 h
10 min, 15 min,
30 min, 1 h or
4 h
2 h
6 h
12 h
24 h
CSV
Setting Range
fixed
fixed
fixed
30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
no
yes
SICAM P850/P855, 7KG85xx, Device Manual
E50417-H1040-C482-A6, Edition 10.2018