Recorder Parameters - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Parameter
Waveform capture setting
Total recording duration
Pretrigger ratio
Record ph-ph voltage
15.3.5.3

Recorder Parameters

Table 15-33
Parameter
Average intervals - Frequency
Short term flicker
Long term flicker
Average interval - Voltage /
Unbalance / Harmonics
Record additional data (I, P, Q,
S etc.)
Recorder of average - Min
Recorder of average - Max
Harmonics
File generation every:
(corresponds to the setting of
the Average interval parameter)
The created PQDIF files can be
downloaded via the user inter-
face or with the IEC 61850
protocol.
Recorded file type
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A9, Edition 06.2021
Default Setting
2.0 s
10%
No
Settings for Measurement Recorder
Default Setting
10 s
10 min
2 h
10 min
no
no
no
Odd
24 h
PQDIF
Operational Indications and Operating Parameters
15.3 Advanced Functions
Setting Range
0.2 s to 3.0 s, increments of 0.2 s
0 % to 30 %, increments of 5 %
No
Yes
Setting Range
fixed
fixed
fixed
1 min
10 min
no
yes
no
yes
no
yes
Even
Odd
All
At average interval:
File generation every:
1 min
2 h (fixed)
10 min
2 h
6 h
24 h
PQDIF
CSV
All