• Press keys 9 and 11 (Fig. 8.14) at the
same time until the value of parameter 11
(10=60 seconds) (Fig. 8.17) is displayed
on the LCD display.
Fig. 8.17
• It is possible to modify parameter 11 by
00=0s to 99=600s using keys 10 or 11
(each increase or reduction by a unit on
the display corresponds to 6 seconds).
• By pressing key 9 (Fig. 8.14) confirmation
of the inserted value is obtained.
• Press keys 9 and 10 (Fig. 8.14) at the
same time to exit without changing the
value (return to the parameters list Fig.
8.16).
• Press sequentially keys, 9 - 10 and then
11 (Fig. 8.14) and hold in for 10 seconds
to exit the "programming mode".
Programming using the REMOTE control
• Press button
for more than 3 seconds to
enter in
mode (Fig. 8.18).
0
21
3
1
8
6
9
1 5
1
2
Fig. 8.18
• Press buttons
time to enter transparent programming
(Fig. 8.19).
- 66 -
ADVANCED COMMISSIONING
and
at the same
Fig. 8.19
• Press buttons
the "PM11" program of the pump post-
circulation (Fig. 8.20).
Fig. 8.20
• To modify the programmed SET, act on
buttons
or
programmed number to flash (Fig. 8.21).
Each step increased or decreased corre-
sponds to 1 second.
Fig. 8.21
• To exit programming, press button .