S4 Beam Sensor & Brackets; Test Keyswitch; How To Install An Angle Bracket And Fit A Beam Sensor - Honeywell GENT S4 Data And Installation

Beam sensor & brackets (for vigilon and nano systems)
Hide thumbs Also See for GENT S4:
Table of Contents

Advertisement

S4 Beam Sensor & brackets

Test Keyswitch

A test keyswitch unit can be connected to the 'beam transmitter' to facilitate simulation of a test fire condition.
The test keyswitch function is supported on Vigilon system only. The keyswitch unit is required to have a
series resistor of value 470W coupled with an end-of-line 10KW resistor wired as illustrated below.
Beam Transmitter base
EM2
OUT5
L2
IN4
C3
L1
0V

How to install an Angle bracket and fit a Beam sensor

The installation of the angle bracket and beam sensor are illustrated by steps
o
require setting of adjusters for sensor to face the opposite sensor assembly, which is normally done
during commissioning.
Metal box
mounted on
a solid wall
Keyswitch wiring if used
4188-969 issue 3_Part 1_07-11_S4 Beam & brackets
O
Input
Loop - In cable
Earth
Metal box
Angle bracket with base
O
There is a maximum cable length
Normal
limit of 15 metres from the 'beam
I
I
transmitter' base to the external
Keyswitch Unit.
O
Active
I
A keyswitch input at the 'beam
transmitter' must be enabled
during commissioning.
FIRE
The wiring is monitored for open
14115-08
or any suitable
and short circuit failure.
keyswitch
On operating the keyswitch it will
cause a ramp down signal to
generate a test fire condition.
j
Loop - Out cable
The numbers in brackets
refer to alternative cable
sleeve markings which may
be used to denote wires.
Cable from the sensor base
Beam Sensor
Data and Installation
o
n
to
. Note steps
and
The Test Keyswitch
connects to terminals
EM2 and C3 in the
base.