Commissioning information

Test

How to test a beam sensor pair

After all the beam sensor pairs are fully commissioned use the appropriate test card (S4-34741-50) to
obscure the beam to simulate a FIRE or FAULT condition.
If a Test Keyswitch unit is connected to a 'beam transmitter' of a beam sensor pair then, if appropriate,
operate the switch to test the beam sensor pair. A test using a Test Keyswitch is not applicable for S4 beam
sensors converted to be backward compatible.
STATE
FIRE test using a test card
0
Use the 50% obscuration Test card in the beam path
1
Use the 50% obscuration Test card in the beam path
Use cardboard to block the beam path for 40 seconds
2
Use the 25% obscuration test card in the beam path
3
Use the 25% obscuration test card in the beam path
Use a cardboard to block the beam path for 40
seconds
Test Card
Adhesive tape
Smoke pole
Transmitter
Transmitter
Floor level
14
A fire indication is given at the '
receiver' only
Also a fire indication is given at the panel.
Flashing
Beam
S4 Beam Sensor & brackets
FAULT test using a card
Use a piece of cardboard to block the
beam path for 40 seconds
N/A
Use a piece of cardboard to block the
beam path for 40 seconds
N/A
and not at a 'Beam transmitter'.
Flashing
Receiver
4188-968 issue 4_Part 2_07-12_S4 mains interface
Beam