Siemens SIMATIC S7-1500 Manual page 104

Technology module, tm posinput 2 6es7551-1ab00-0ab0
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

The following table shows the module-specific error codes and their meaning for parameter
data record 128 when using an SSI absolute encoder.
Table B- 3
Error codes for parameter validation (SSI absolute encoder)
Error code in STATUS parame-
ter (hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
00
DF
80
B1
01
DF
80
B2
00
DF
80
E0
01
DF
80
E0
02
DF
80
E1
00
DF
80
E1
11
DF
80
E1
12
DF
80
E1
13
DF
80
E1
18
DF
80
E1
19
DF
80
E1
1A
DF
80
E1
1B
DF
80
E1
1C
DF
80
E1
25
DF
80
E1
26
DF
80
E1
27
DF
80
E1
28
DF
80
E1
29
DF
80
E1
2B
Technology module TM PosInput 2 (6ES7551-1AB00-0AB0)
Manual, 06/2018, A5E03982218-AB
Meaning
Data record number unknown
Length of data record incorrect
Slot invalid or not accessible
Wrong version
Error in the header information
Parameter invalid: No detailed information
available
"Operating mode" parameter invalid
"Reaction to CPU STOP" parameter invalid
"Signal type" parameter invalid
"Set function of DI" parameter configured the
same for DIn.0 and DIn.1.
"Edge selection" parameter invalid
"Input delay" parameter invalid
"Set output" parameter invalid
"Count direction" parameter invalid
"Update time" parameter invalid
"Reference speed" parameter invalid
1
"Measured variable" parameter invalid
"Time base for velocity measurement" parame-
ter invalid
"Increments per unit" parameter invalid
2
"Comparison value 0" parameter invalid
"Comparison value 1" parameter invalid
Parameter data record
B.2 Parameter validation error
Remedy
Enter valid number for data record.
Enter valid value for data record length.
Check whether module is inserted or removed.
Check assigned values for parameters of the
WRREC instruction.
Check byte 0.
Enter valid values.
Check byte 1.
Correct the length of the parameter blocks.
Check all parameter values.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter different parameter values for DIn.0 and DIn.1.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter parameter value from range 0 to 25000000
Enter parameter value from range 6.00 to
210000.00
.
D
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value.
Enter valid parameter value:
Comparison value 0 < comparison value 1
.
D
103

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et-200mp

Table of Contents