10.2.2 System FT128

"FAULT: No reply AAU x.
The contact with the AA unit is interrupted.
connections. Is a correct / complete SSD download (via Win128) performed?
Check the address setting, SW mode setting, etc. See also chapter "Restart",
page 19.
"FAULT: AAU x "
The AA unit is programmed (via Win128) as another type of unit or there is a
fault in the AA unit.
"FAULT: Site specific data (SSD), AAU x.
See chapter "Restart", page 19.

10.2.3 System FT1020G3

"FAULT: No reply, alert annunciation unit xx, control unit xx
The contact with the external AAU is interrupted. Check the cable and all
connections. Is a correct / complete SSD download (via WinG3) performed?
Check the address setting, SW mode setting, etc. See also chapter "Restart",
page 19.
"FAULT: Alert annunciation unit xx"
The AAU is programmed (via WinG3) as another type of unit or there is a fault
in the AAU.
"FAULT: External presentation unit xx, control unit xx"
The AAU is programmed (via WinG3) as another type of unit or there is a fault
in the AAU.
"FAULT: Site specific data, alert annunciation unit xx, control unit xx.
See chapter "Restart", page 19.
Technical Description
Check the cable and all
22
AAU 1736 – Rev 1