Toshiba MMU-P0121H Service Manual page 54

Modular multi system, indoor unit, outdoor unit.
Hide thumbs Also See for MMU-P0121H:
Table of Contents

Advertisement

Check
Detected
Check code
code
position
name
bE
Interface Low pressure
protective
operation
cF
Indoor
Communication
error between
indoor MCU
d1
Interface Outdoor
inverter set up
alarm
d2
Interface Fixed-speed
outdoor unit
alarm
d3
Inverter
TH sensor
alarm
d4
Interface TK1 sensor
alarm
d5
Interface TK2 sensor
alarm
Cause
Trouble detection condition
(Position)
Protection
Low pressure Ps detected
when low
lower than 0.02MPa.
pressure Ps
lowered.
Communication between MCU
Lead wire
interrupted for 50 seconds.
between indoor
main P.C.
board (MCC-
1361) and
indoor motor
P.C. board
(MCC-1382)
Outdoor
There were multiple outdoor
inverter units
inverter units in 1 line.
are duplicated.
Fixed-speed
Inverter outdoor unit received
outdoor unit
an alarm code from fixed-
protection
speed outdoor.
Temp. sensor
Sensor resistance value was
(TH) to detect
infinity or zero (Open, Short).
overheating of
IPDU
microprocessor
Temp. sensor
Sensor resistance value was
(TK1) to detect
infinity or zero (Open, Short).
oil level
Temp. sensor
Sensor resistance value was
(TK2) to detect
infinity or zero (Open, Short).
oil level
3-51
Check item (Position)
• Check for refrigerant shortage.
• Check outdoor service valves.
(Gas side, Liquid side are fully open.)
• Check for blockage of outdoor PMV.
1) Refrigerant choke circuit (PMV A)
2) Liquid line check valve
(Cooling only model)
• Check discharge temp. TD sensor
error.
• Check low pressure Ps sensor error.
• Check indoor filter blockage.
• Check refrigerant pipe blockage.
• Check outdoor fan operation.
(In heating)
• Check connection between connector
(CN28) of indoor main P.C. board
(MCC-1361) and connector (CN27) of
indoor motor P.C. board (MCC-1382).
• Check failure of indoor main P.C.
board (MCC-1361).
• Check failure of indoor motor P.C.
board (MCC-1382).
• Check No. of connected inverter
outdoor units.
• Check SW08/bit 2 set up on outdoor
P.C. board (interface).
• Check outdoor P.C. board (interface).
• Check the check code of fixed-speed
outdoor unit.
• Convenient functions
If keeping SW04 pushed for 5 seconds
or more under condition that [d2] is
displayed on the 7 segment display of
the inverter outdoor, fan of the outdoor
unit which stops in emergency
operates.
If keeping SW04 and SW05 pushed
concurrently, the normal outdoor unit
fan operates.
If pushing SW05 alone, the fan
operation is released.
• Temp. sensor incorporated with IGBT
has failed. → Replace IPDU P.C.
board.
• Check connector connection of TK1
sensor.
• Check characteristics of TK1 sensor
resistance value.
• Check outdoor P.C. board (interface)
error.
• Check connector connection of TK2
sensor.
• Check characteristics of TK2 sensor
resistance value.
• Check outdoor P.C. board (interface)
error.