Toshiba MMU-P0121H Service Manual page 53

Modular multi system, indoor unit, outdoor unit.
Hide thumbs Also See for MMU-P0121H:
Table of Contents

Advertisement

Check
Detected
Check code
code
position
name
b5
Indoor
Indoor outside
input alarm
b6
Indoor
Indoor outside
interlock
b7
Indoor
Indoor unit
No. 2 to 16 in
grouping
b9
Indoor
Indoor
pressure
sensor alarm
bb
Interface Discharge
temp. TD2
alarm
bd
Interface Mg-SW
deposit
protective
operation
Cause
Trouble detection condition
(Position)
Alarm display
By voltage Vemg to be input
by outside
in outside alarm input terminal
input
(Vemg < 1.25V was detected
for 60 seconds.)
Display of
• By voltage value Vemg to be
outside
input in outside alarm input
interlock input
terminal
(Vemg < 3.75V was
detected for 60 seconds.)
Indoor unit
Server unit error in group
alarm in
operating
group
operating
Indoor
Indoor pressure sensor output
pressure
was zero.
sensor
(After judgment, operation
transmits to automatic backup
operation.)
Discharge
The protective stop when
temp. (TD2)
discharge temp. TD2
protection
exceeded 130°C and repeats
for 3 times or more.
Fixed-speed
30 seconds passed after
Mg-SW
outdoor (compressor) stops,
deposit
1 Discharge temp. 135°C for
protective
fixed-speed compressor
control is
was detected.
operating.
2 Ps pressure < 0.02MPa and
TD ≥ 60°C were detected.
3 Pd pressure ≥ 3.2MPa and
TD ≥ 80°C were detected.
[NOTE]
During control operation, if
high pressure Pd becomes
3.2MPa or more, the outdoor
fan operates.
The indoor PMV and outdoor
PMV are forcibly opened, and
the cooling cycle is formed.
3-50
Check item (Position)
• When outside equipment is connected to
connector (CN21)
1) Check outside equipment error.
2) Check indoor P.C. board error.
• When outside equipment is not
connected to connector (CN21)
1) Check indoor P.C. board.
• When outside equipment is connected to
connector (CN21)
(Indoor main P.C. board (MCC-1361)).
1) Check outside equipment error.
2) Check failure of indoor main P.C.
board (MCC-1361).
• When outside equipment is not
connected to connector (CN21)
(Indoor main P.C. board (MCC-1361)).
1) Check indoor main P.C. board
(MCC-1361).
Check each indoor unit with the remote
controller
• Check connection and wiring of connector
(CN23) of indoor pressure sensor and
indoor main P.C. board (MCC-1361).
• Check indoor pressure sensor error.
• Check failure of indoor main P.C. board
(MCC-1361).
• Check service valves.
(Gas side, Liquid side are fully open.)
• Check for blockage of outdoor PMV.
1) Refrigerant choke circuit (PMV A)
2) Cooling bypass circuit (PMV B)
3) Liquid line check valve
(Cooling only model)
• Check TD2 sensor resistance value
characteristics
• Check refrigerant shortage, piping
blockage
• Check contact of the fixed-speed Mg-SW.
• Check for refrigerant shortage.
• Check discharge temp. TD sensor error at
fixed-speed unit side.
• Check Pd and Ps pressure sensors error.