Service P.C. Board Selection Information
[Concealed duct, 1-way air discharge cassette type]
Service P.C. board selection corresponded table (Main P.C. board MCC-1361)
The indoor control P.C. board (MCC-1361) can correspond to multiple models. When replacing P.C. board
assembly, set the DIP switch, rotary switch, and jumper(s) according to the following description.
Switch set up
1
SW01
Indoor unit No.
2
SW02
Network address
3
SW03
4
SW05
(Bit 1)
5
SW05
(Bit 2)
6
SW06
7
SW07
8
SW08
Horse power set up : Match to set up contents of P.C. board before replacement.
Jumper set up
1 Match to the set up contents of P.C. board before replacement except for J11, J12 and J20.
2.
J20
: If Auto-turn-louver is equipped, cut J20.
3.
J11, J12
: See the P.C. board before relacement, according to the table below, cut jumper(s) if necessary.
Before replacement
J11
J12
¡
¡
¡
X
¡
X
X
X
: Match to No. which the rotary switch is set up.
: Master unit ...... 1
: Server units ..... 2 to 16
: Match to set up contents of P.C. board before replacement.
: Match to set up contents of P.C. board before replacement.
: Match to set up contents of P.C. board before replacement.
: Set to OFF side.
: Match to set up contents of P.C. board before replacement.
: Match to set up contents of P.C. board before replacement.
J11
J12
¡
X
¡
X
¡
X
X
X
Service P.C. board part name : <MCC-1361>
3-120
Service P.C. board setting
Applicable models
1-way air discharge cassette type
Concealed duct type
All models
All models
All models
CM02C06S
SN
4316V165
O : Provided, X : None (cut)