Programming Errors - ABB SACE Emax 2 Series Instructions For Use Manual

Low voltage air circuit-breakers
Table of Contents

Advertisement

Programming errors If during the programming of the parameters an attempt is made to violate certain limitations, the trip unit
24 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
blocks the saving procedure and signals the error:
Type of error
L Th ≥ S Th
S Th ≥ I Th
L Th ≥ S2 Th
S2 Th ≥ I Th
L Th ≥ D Th
D Th ≥ I Th
D Zone Sel = On while S / S2/ G / Rc = On
S(V) t20 and S(V) I20 error
RQ Q24 > Q25
SYNCHRO parameters error
ROCOF t28 error
And the MCR enabled together
High priority alarm
Rc toroid error
Internal neutral config error
Change of datalogger number with datalogger not
stopped
Error Reverse pole order
Programming Session Timeout
Error description
Errors in the adjustment of the protection thresholds
Errors in the adjustment of the protection thresholds
Errors in the adjustment of the protection thresholds
Errors in the adjustment of the protection thresholds
Errors in the adjustment of the protection thresholds
Errors in the adjustment of the protection thresholds
Activation of Zone Selectivity with protections S, S2,
G or Rc enabled
Incorrect configuration of S(V) protection
Incorrect configuration of RQ protection
Error in the parameters of the Ekip Synchrocheck
module
Incorrect configuration of ROCOF protection
Simultaneous enabling of the protections I and MCR
Protection and delay alarms present during
programming
Attempt to activate the Rc toroid without Ekip
Measuring or Rating Plug of the Rc type
It tries to set the internal neutral setting with a value
that is not allowed
Change datalogger parameters with datalogger
active
Change of the parameter "pole order" with a half
size circuit-breaker.
Timeout for saving data
Ekip Touch protection trip unit | 16 - Self-diagnosis
ABB | SACE Emax 2