Availability (Performance); Summary Table Of Hi-Touch Protections; Hi-Touch Protections - ABB SACE Emax 2 Series Instructions For Use Manual

Low voltage air circuit-breakers
Table of Contents

Advertisement

8 - Hi-Touch protections

Availability (Performance)

The following is a complete list of the protections (and related parameters) available with all the Ekip Hi-Touch and Ekip G Hi-Touch trip units, in
the Protections and Advanced menus:
Name
Protection against
S2
Selective short-circuit
(3)
D
Directional short circuit
(6)
UV2
Minimum voltage
OV2
Maximum voltage
UF2
Minimum frequency
(5)
OF2
Maximum frequency
(5)
Double configuration of the
Set A-B
protections
(1)
Detailed description in the Design Engineer's manual.
(2)
Locking Function available via Ekip Connect.
(3)
For all the UL versions the maximum time allowed by the trip unit is 0.4 seconds. If a higher value is set, the trip unit signals the error and forces
the parameter to 0.4 seconds.
(4)
Directional Zone Selectivity works as an alternative to S and G Zone Selectivity.
(5)
Protection not active for voltages <30V.
(6)
The protection does not detect the direction of fault current for voltages < 5V.

Summary table of Hi-Touch protections

ABB
ANSI
Threshold
(4)
I5 = 0.6...10 In
S2
50 TD
step = 0.1 In
I7 Fw/Bw = 0.6...10 In
D
67
step = 0.1 In
U15= 0,05....0,98 Un
UV2
27
step = 0.001 Un
U16= 1....1,5 Un
OV2
59
step = 0.001 Un
f17= 0,9....1 fn
UF2
81L
step = 0.001 fn
f18= 1....1,1 fn
OF2
81H
step = 0.001 fn
16 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
Threshold
Time
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Tolerance threshold
Time
± 7 % If ≤ 6 In
t5 = 0.05...0.8 s
± 10 % If > 6 In
step = 0.01 s
t7 Fw/Bw =
± 7 % If ≤ 6 In
0.1...0.8 s
± 10 % If > 6 In
step = 0.01 s
t15 = 0.05...120 s
± 2 %
step = 0.01 s
t16 = 0.05...120 s
± 2 %
step = 0.01 s
t17 = 0,06...300 s
± 1 %
(5)
step = 0.01 s
t18 = 0,06...300 s
± 1 %
(5)
step = 0.01 s
Auxiliary functions
(1) (2)
Trip enable, Zone Selectivity, Startup enable, lock
Trip Enable, Directional Zone Selectivity
Locki, Min Angle Direction
Trip Enable, Lock
Trip Enable, Lock
Trip Enable, Lock
Trip Enable, Lock
Default set, Activation event, Activation delay
Calculation
formula t
(1)
t
t
= t5
t
t
= t7
t
t
= t15
t
t
= t16
t
t
= t17
t
t
= t18
t
Ekip Touch protection trip unit | 8 - Hi-Touch protections
ABB | SACE Emax 2
, Startup enable,
(4)
Tolerance t
(2)
t
The better of the two
values:
± 10 % or ± 40 ms
The better of the two
values:
± 10 % or ± 40 ms
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
The better of the two
values:
± 10 % (min=30ms) or ±
40 ms (for a time set < 5 s)
/ ± 100 ms (for a time set
> 5 s)
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
Continued on the next page