Siemens SIRIUS 3RW5 Manual page 97

Soft starters and solid-state switching devices, ethernet/ip communication module
Hide thumbs Also See for SIRIUS 3RW5:
Table of Contents

Advertisement

Object
Byte
Bit Data
No.
format
43
345
0
USINT Creep speed factor right
44
347
0
USINT Creep speed torque right
198
349
0
USINT Creep speed factor left
199
351
0
USINT Creep speed torque left
2337
353
0
UINT
2338
355
0
UINT
2340
357
0
USINT Current lower limit error
2341
359
0
USINT Current lower limit -
2250
361
0
UDINT Active power reference value
2251
365
0
UINT
2252
367
0
UINT
2254
369
0
USINT Active power lower limit error
2255
371
0
USINT Active power lower limit -
2317
373
0
UINT
2320
375
0
USINT Starting time lower limit -
2218
377
0
Bit4
21
379
0
Bit4
SIRIUS 3RW5 EtherNet/IP communication module
Manual, 05/2019, A5E45131885002A/RS-AA/001
Parameters
Current upper limit error
Current upper limit -
maintenance demanded
maintenance demanded
Active power upper limit error
Active power upper limit -
maintenance demanded
maintenance demanded
Starting time upper limit -
maintenance demanded
maintenance demanded
Asymmetry limit warning
Asymmetry limit error
Range of values
[encoding]
3 ... 21
[3 ... 21]
20 ... 100 %
[4 ... 20]
3 ... 21
[3 ... 21]
20 ... 100 %
[4 ... 20]
50 ... 400 %
[50 ... 400]
[0] Deactivated
50 ... 400 %
[50 ... 400]
[0] Deactivated
20 ... 100 %
[20 ... 100]
[0] Deactivated
20 ... 100 %
[20 ... 100]
[0] Deactivated
0 ... 2 000 000 W
[0 ... 2 000 000]
0 ... 400 %
[0 ... 400]
0 ... 400 %
[0 ... 400]
0 ... 100 %
[0 ... 100]
0 ... 100 %
[0 ... 100]
0 ... 400 %
[0 ... 400]
0 ... 100 %
[0 ... 100]
10 ... 60 %
[2 ... 12]
[0] Deactivated
10 ... 60 %
[2 ... 12]
[0] Deactivated
Appendix
A.9 Dataset Object
Incre-
3RW55
1)
ment
[D
]
2)
1
r/w
[7]
5 %
r/w
[10]
1
r/w
[7]
5 %
r/w
[10]
5 %
r/w
[0]
5 %
r/w
[0]
5 %
r/w
[0]
5 %
r/w
[0]
1 W
r/w
[0]
1 %
r/w
[0]
1 %
r/w
[0]
1 %
r/w
[0]
1 %
r/w
[0]
1 %
r/w
[0]
1 %
r/w
[0]
5 %
r/w
[0]
5 %
r/w
[6]
97