Appendix
A.9 Dataset Object
A.9.4
Parameters
Both read (get, r) and write (set, w) access to the parameters is possible. The Dataset Object
"parameter" is not supported by the 3RW52 soft starter.
The instance and attribute ID of all parameters is 25408 (0x6340).
Object
Byte
Bit Data
No.
format
-
273 ...
-
-
274
2313
275
0
Bit4
2315
277
0
UINT
130
279
0
UDINT Rated operational current Ie
92
Parameters
Reserved
Automatic parameterization
Preset starting time
SIRIUS 3RW55 soft starter,
High Performance, 13 A,
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter,
High Performance, 18 A,
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter,
High Performance, 25 A,
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter,
High Performance, 32 A,
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter,
High Performance, 38 A,
3-phase controlled, motor
overload protection, torque
control
SIRIUS 3RW55 soft starter,
High Performance,
25 A / 690 V, 3-phase
controlled, motor overload
protection, torque control
Range of values
[encoding]
-
[0 ... 2]
[0] Off
[1] ON - with preset starting time
[2] ON - with preset starting time and
current limit
0 ... 360 s
[0 ... 3 600]
-
2.5 ... 22.5 A
[250 ... 2 250]
3.5 ... 31.1 A
[350 ... 3 110]
5 ... 43.3 A
[500 ... 4 330]
6.5 ... 55.4 A
[650 ... 5 540]
7.5 ... 65.8 A
[750 ... 6 580]
5 ... 43.3 A
[500 ... 4 330]
SIRIUS 3RW5 EtherNet/IP communication module
Manual, 05/2019, A5E45131885002A/RS-AA/001
Incre-
3RW55
1)
ment
[D
]
2)
-
-
-
r/w
[0]
0.1 s
r/w
[100]
0.01 A
r/w
3)
0.01 A
[250]
0.01 A
[350]
0.01 A
[500]
0.01 A
[650]
0.01 A
[750]
0.01 A
[500]